Electrician Safety Rules
The company you work for as an electrician probably has a list of safety
rules in your employee handbook. Be sure to look over these rules. Make
suggestions to your foreman for additional rules which may help other
electricians.
Here is a sample of electrician safety rules which may be useful to you. You
may copy these rules as you may deem useful to you.
Carry a first aid kit in your tool box.
Maintain all tools in like new operating condition.
Report selective tools to your supervisor.
Tag out defective equipment so others will not use them.
Replace personal tools as needed.
Secure all tools and equipment to avoid tampering and theft.
Verify GFCI protection works for all power circuits.
Avoid hazardous work positions above and below ground.
Use protective gear appropriate to the environment.
Clean up work area before, during and after work.
Lock out disconnects when working on equipment.
Operate equipment according to manufacturers directions.
Treat minor injuries properly. Report all injuries.
Lift heavy material properly. Seek help as needed.
De energize circuits while making repairs to avoid electric shock.
Observe fellow employees for safety compliance.
Stay well clear of hostile confrontation with other workers.
Do not wear loose or excessive jewelry.
Proper footwear is mandatory.
Keep a spare set of work clothes handy just in case.
Verify that pets on the job are harmless or ask that they be secured.
Leave any job site to avoid injury when you are concerned.
Wear clean clothing every day.
Drive to and from job locations very cautiously.
Keep material in work vehicles in an organized manner.
Position load in vehicles to avoid injury due to load shifts.
Here are a set of safety rules from Lawrence Livermore National Laboratory (LLNL)
SOURCE:



Document
16.1
Electrical Safety
Revision Definitions
Approval date: February 27, 1996
Editorial Revision date: July 1, 2003


Table of Contents

This document contains general requirements for all Laboratory work
involving the use of electrical equipment and systems. Appendix
A contains terms and definitions and Appendix B, the
effects of electrical energy on humans. All managers, designers, users,
installers, and others who service or operate electrical equipment--including
those used for research and development (R&D)--shall comply with these
requirements.
More specific information about electrical work can be found in
Document 16.2, "Work and Design Controls for Electrical
Equipment," and Document
16.3, "LLNL Authority Having Jurisdiction Requirements for Approving
Electrical Equipment, Installation, and Work," in the Environment,
Safety, and Health (ES&H) Manual. In addition, Laboratory programs may
consult the Electrical Safety Advisory Board (ESAB) for further guidance on
electrical work. The ESAB was chartered on February 20, 1996, and is the
Laboratory's technical resource for electrical safety issues. The Board
comprises a chair and several members from the Hazards Control Department,
Electronics Engineering, Scientific Programs, and Plant Engineering who are
knowledgeable in electrical safety. The chair is a member of the Safety Programs
Division and is appointed by the Hazards Control Department Head. The other
members are nominated by the chair and approved by the Hazards Control
Department Head.
Electricity is used in many different ways at LLNL. Each application has its
own combination of hazards that includes the potential of electric shock, fire,
and burns. Thus, it is essential for all employees, including supplemental labor
and subcontractor employees, to be aware of the hazards associated with
electrical work and use appropriate protective methods to minimize the risk of
an injury or accident.
Appendix B contains more detailed information about
the effects of electrical energy on humans.
Only qualified and authorized individuals are permitted to perform
electrical work at LLNL. A qualified person is one who has the required skills
and knowledge to perform electrical work safely. Such individuals must be aware
of the hazards associated with electrical work (see Appendix B
for details) and the methods for reducing the risk of electrical accidents that
can result from unsafe equipment, adverse environmental conditions, and unsafe
acts.
Whenever possible, all circuits or equipment shall be de-energized before
beginning any work. Work on energized circuits shall only be performed by
authorized workers, as described in Document
16.2. In addition, these workers shall use
 |
Proper design, fabrication, installation, and documentation techniques.
 |
Proper operational and maintenance procedures.
 |
Electrical equipment approved by a nationally recognized testing
laboratory (NRTL).
 |
Proper personal protective equipment (PPE).
|
| | |
In support of Lab-wide electrical safety, management shall take a proactive
approach when dealing with the root causes of employees' concerns, near-misses,
and incidents or accidents involving electrical hazards.
All electrical equipment, components, and conductors should be listed,
labeled, and approved by an NRTL for their intended purpose. Custom-made and
installed equipment can be approved for use, by the Electrical Authority Having
Jurisdiction (AHJ), if built according to specific standards (e.g., Underwriters
Laboratories [UL] 508 or one of the ANSI C series standards). Appropriate
documentation for such equipment shall be maintained on file.
When building, repairing, or modifying electrical systems, NRTL-approved
equipment must be used if available. Non-NRTL-approved equipment (e.g.,
shop-made extension cords) shall be built in accordance with an approved design,
as specified in Document
16.3.
Document
17.1, "Explosives," in the ES&H Manual provides specific
guidance for explosives work and for work in explosives areas. Assure an
Explosives Safety Engineer has reviewed the process prior to starting work in
explosives facilities or areas.
Any live electrical parts shall be positively de-energized when working on
or near electrical circuits, equipment, or systems. Circuits and equipment must
be considered energized until isolated, locked out and tagged , and verified
with an appropriate testing device as described in
Document 12.6, "LLNL Lockout/Tagout Program," in the ES&H
Manual. Where it is possible for the circuits to be energized by another
source, or where capacitive and/or inductive devices (including cables) may
retain or build up a charge, circuits shall be grounded and shorted. Exceptions
to this paragraph may be permitted when the requirements in
Document 16.2 are fulfilled.
Additionally, the following precautions shall be observed to improve safety
in the workplace:
 |
 |
Identify and report to your supervisor potential electrical hazards or
unexpected occurrences or incidents (i.e., discharges or arcs when applying
grounds to circuits thought to be de-energized), including near misses.
 |
Anticipate potential electrical problems and hazards.
 |
Do not rush to finish a job; never bypass approved procedures.
 |
Plan and analyze for safety during each step of any electrical work.
 |
Keep accurate records (e.g. system one-line drawings, panel schedules,
etc.) for electrical or electronic systems.
 |
Have significant safety-related work (e.g., work requiring an OSP)
independently verified.
 |
Use properly rated test equipment and verify its condition and operation
before and after use.
 |
Know applicable emergency procedures.
|
| | | | | | | |
A clear working space shall be maintained in the front, back, and on each
side of all electrical enclosures and around electrical equipment for safe
operation and to permit access for maintenance and alteration. Refer to the
documents listed in this section as required. (NOTE: The National Electrical
Code (NEC) is available from the Technical Information Department (TID) Library
and the Plant Engineering Library. You may also contact the Hazards Control
Department for additional information about the NEC):
 |
NEC Article 110-26, "Spaces about electrical equipment, (600 volts
or less)."
 |
NEC Article 110-32, "Work space about equipment (over 600
volts)."
 |
NEC Article 110-33, "Entrance and access to work space."
 |
NEC Article 110-34, "Work space and guarding (over 600
volts)."
 |
|
| | | |
In addition to the NEC, the IES Lighting Handbook (latest edition) specifies
the following requirements for electrical equipment:
 |
Adequate illumination shall be provided for all working spaces around
electrical equipment.
 |
The control switches for light circuits shall be positioned away from
exposed energized circuits and other potential electrical hazards.
|
|
Construction Power and Lighting. Temporary wiring for electric power
and lighting is permitted during periods of construction, remodeling,
maintenance, repair, or demolition of equipment or structures and during
emergencies. Temporary wiring does not mean a "reduced" level of
safety or quality, as this wiring must still conform to certain criteria for
electrical work.
Temporary wiring shall have a temporary wiring tag attached to it with the
following information:
 |
Review/approval and signature of the facility manager, area supervisor,
lead experimenter, construction inspector, or Plant Engineering Electrician
Shop supervisor and the signature of the appropriate ES&H Team
industrial safety representative.
 |
The reason for the temporary wiring (i.e., emergency, construction,
test, and/or research and development).
 |
Installation date.
 |
Name, phone number, and pager number (if applicable) of the person
installing the temporary wiring tag.
|
| | |
In addition, temporary wiring
 |
Shall be approved or identified as suitable for installation and
installed in accordance with the rules prescribed in the current edition of
the NEC and 29 CFR 1910 and 1926.
 |
Shall be protected from accidental damage.
 |
Shall be removed as soon as the prescribed activity is completed. It
shall not be used as a substitute for permanent wiring.
 |
Shall be color coded in accordance with Plant Engineering or Electronic
Engineering standards.
 |
May be used during an "off-shift working hour" emergency. On
the day of installation, a temporary wiring tag shall be completed and
attached to the wiring so that it is readily visible. Approvals for the
wiring tag must be obtained on the first regular workday after the
emergency.
|
| | | |
Switches or other means shall be installed to permit the disconnection of
all ungrounded conductors of each temporary circuit. All lamps used for
temporary illumination shall have a suitable fixture or lamp holder with a guard
to prevent damage or accidental contact with energized parts.
Experiments. Temporary wiring may be used for experimental and
developmental equipment. There is no time limit on how long the wiring can
remain in place, except that it must be removed upon completion of the
experiment. Temporary wiring tags are not required for temporary wiring within
experimental systems. However, they are required for the power feeder to the
power distribution points of experimental systems. The wiring tag on these
systems shall contain the same information as previously described.
Extension Cords. Observe the following precautions when using
extension cords. Note that extension cords for normal office use do not require
a temporary wiring tag.
 |
Use only three-wire extension cords and cables that conform to the
rating, grounding, and non-interchangeability stated in NEC Article 210-7
(Receptacles and Cord Connectors).
 |
Check extension cords before use to ensure they are adequate for the
intended purpose. Plug high-current equipment (e.g., space heaters, hot
plates, and coffee pots) directly into a wall receptacle whenever possible.
 |
Use only one extension cord for lamps, appliances, or other equipment in
conjunction with the power supply cord. Laboratory practice prohibits the
use of multiple extension cords (daisy chaining) that will increase
resistance in an electrical circuit, which in turn will increase heating of
conductors, receptacles, and plugs.
 |
Inspect extension cords for damage before placing them in service and
daily during use. Only qualified and authorized persons can repair extension
cords; this must be done in a manner approved by the manufacturer. Replace
damaged cords with ones listed by an NRTL. Contact the ES&H Team for
guidance, if necessary.
 |
For receptacles connected to circuits with different voltages,
frequencies, or current (ac or dc) on the same premises, use a design such
that the attachment plugs on the circuits are not interchangeable (see Section
3.7 for details). All extension cords shall be listed or labeled by an
NRTL.
|
| | | |
Only high-visibility orange or yellow extension cords shall be used outdoors
and with portable or integral ground-fault circuit interrupters (GFCIs).
Multiple Outlet Boxes. Observe the following precautions when using
multiple outlet boxes:
 |
Each multiple outlet box shall be plugged into a wall receptacle. Use of
one outlet box to provide power to one or more outlet boxes is not
permitted.
 |
Outlet boxes shall not be used to provide power to space heaters, hot
plates, coffee pots, or other high-current loads. These types of appliances
have caused outlet boxes to burn up.
|
|
Note that multiple outlet boxes used in offices, as well as those used to
provide surge protection for computers, do not require a temporary wiring tag.
Flexible Cords and Cables. Flexible cords and cables shall comply
with the requirements in NEC Article 400 (Flexible Cords and Cables). They shall
not be
 |
Used as a substitute for fixed wiring of a structure.
 |
Attached to building surfaces.
 |
Routed through holes in walls, ceilings, or floors; or through doorways,
windows, or similar openings.
 |
Concealed behind building walls, ceilings, or floors.
 |
Wired with a plug or connector that does not have dead-front
construction or strain relief. "Dead-front construction" is
defined as electrical equipment built so that it is "without live parts
exposed to a person on the operations side of the equipment."
 |
Placed where they could present a trip or fall hazard.
 |
Used when the cord insulation is damaged, cracked, or spliced; or when
the ground pin is missing from the end of the male cord plug.
 |
Installed in raceways, except as otherwise permitted by the NEC.
|
| | | | | | |
Individual conductors of a flexible cord or cable shall not be smaller than
those listed in Table 400-5(A) and (B) of NEC Article 400.
Article 240-4 of the NEC (Protection of Flexible Cords and Fixture Wires)
states that flexible cords, including extension cords, shall be protected
against overcurrent in accordance with their amperage ratings (see Tables
400-5(A) and 400-5(B)). NEC Article 400-14 states that flexible cords and cables
inserted through holes in covers, outlet boxes, or similar enclosures shall be
protected by bushings or fittings.
The Laboratory uses many different voltages, frequencies, and current (ac or
dc) in power systems and equipment. Thus, it is essential to ensure that such
equipment cannot be inadvertently connected to the wrong power source. For
specific purposes, voltage, and current ratings, use a plug or receptacle that
fully complies with the requirements in ANSI C73. See the configuration chart
(from ANSI C73) in the NFPA National Electrical Code Handbook for information
about general-purpose locking and nonlocking plugs and connectors. Use of the
National Electrical Manufacturers Association (NEMA) connectors may not be
appropriate for all research and development applications. Contact Electronics
Engineering Specifications and Standards Group for guidance, if necessary.
Ground-fault circuit interrupters-either circuit breakers or portable
ground-fault interrupting receptacles-shall be used for
 |
All 125-V single-phase, 15-A and 20-A receptacles within 6 feet of a
sink or installed outdoors.
 |
Temporary wiring outdoors.
 |
Wherever employees will be using electrical equipment around water or in
damp environments.
|
| |
Unlike fuses or standard circuit breakers, which are designed to protect
equipment from overcurrent, GFCIs are designed to protect personnel from serious
injury or death.
Article 305-6 of the NEC (Ground-Fault Protection for Personnel) requires
GFCI protection of all 125 V, single phase, 15, 20, and 30-Amp receptacles that
are associated with temporary wiring on construction sites. LLNL requires the
use of GFCIs for any type of construction work to ensure personnel protection,
even if the receptacle is part of the permanent wiring of the building.
Laboratory practice is to provide its employees and subcontractors with at
least the same level of protection from electric shock as they would have in
their own homes. NEC Article 210-8 (Ground-Fault Circuit-Interrupter Protection
for Personnel) specifies that GFCIs must be installed in the following
locations:
 |
Dwellings where 125-V single-phase, 15-A and 20-A receptacles are
installed outdoors.
 |
Bathrooms, garages, and crawl spaces at or below grade.
 |
Unfinished basements.
 |
Where receptacles on countertop surfaces are within 6 ft of a sink.
|
| | |
Thus, all the aforementioned areas within LLNL shall have receptacles with
GFCI protection.
Exceptions to these requirements are:
 |
Laboratory areas where receptacles are required (other than on counter
tops) to supply power to specific equipment (i.e., receptacles dedicated to
refrigerators or other heavy equipment).
 |
Line filters and other power supply components in many electronic
instruments. These instruments draw sufficient capacitive current to trip a
GFCI and therefore are not designed to be connected to GFCI-protected
circuits. They also shall not be installed in wet or damp locations.
|
|
Portable electrical equipment or tools shall always be inspected to identify
defects; defective equipment shall be removed from service immediately. Portable
electrical equipment shall be connected to a portable GFCI (or a circuit that
contains a GFCI) when used outdoors, in damp locations, in any unsafe
environment, or for indoor or outdoor construction. Ordinarily, the casings for
portable electrical equipment are grounded. If it is necessary to operate this
type of equipment with other than a grounded equipment casing, suitable
barriers, guards, or shields shall be installed to protect personnel while
working on or near the equipment. In addition, a safety procedure shall be
written describing the controls for safe operation of the equipment.
Receptacles and flexible cords can be used to connect electrical appliances
and equipment (e.g., fans, machine tools, and pumps) to power sources.
Receptacles used on a two-wire, single-phase portable generator (or
vehicle-mounted generator) with a rating of not more than 5 kW (where the
circuit conductors are insulated from the frame and all other grounded surfaces)
do not need to be GFCI protected.
All electrical apparatus, equipment, and systems shall be grounded in
accordance with NEC Article 250 (Grounding) and ANSI standards. The conductor
used for grounding shall meet the following criteria:
 |
Be permanent and continuous.
 |
Facilitate operation of the circuit's protective devices.
 |
Have sufficiently low impedance to limit the voltage to ground to a safe
level at all frequencies and fault-current conditions anticipated.
 |
Have the capacity (size and rating) to safely conduct any fault current
that may be imposed on it for the time required for protective device
operation.
|
| | |
Guidelines for proper grounding of programmatic equipment and systems can be
found in the Electronics Engineering Department Grounding Guidelines:
Practical Examples for Power Systems at LLNL (UCID-19752).
A static charge is an imbalance of electrons on objects (matter) that can
build up on all matter and transfer from one object to another by conduction or
induction. The discharge of static electricity can cause shock or a fire or
explosion. Although this type of shock is painful, it is not normally physically
hazardous and therefore is not considered reportable as an electric shock. It
should be noted, however, that injuries may result from reaction to the shock
(i.e., by a person rapidly pulling his/her hand away from a metal object and
hitting an elbow against a wall or cabinet).
Equipment and Personnel Guidelines. When working with electrical
equipment, employees shall follow the guidelines below for their own protection
and that of the equipment:
 |
Grounding of the metal parts or enclosures will continuously discharge
static. Therefore, wrist straps and other connections used to ground
employees shall be solidly grounded where static-safe workstations are used
for semiconductor, electronic, or explosive work. Grounding prevents the
wrist strap from becoming a shock hazard in the event of a short circuit
from a voltage to the wrist-strap conductor.
 |
Bonding will equalize the potential between two adjacent noncurrent-carrying
metal parts or enclosures. Thus, only approved or listed grounding clamps
are acceptable for static bonding and grounding. Alligator clamps are not
acceptable.
 |
Dust is attracted to the face of the video display terminal because of a
static charge of approximately 25,000 V. Therefore, never clean the glass
face of a computer monitor while the computer is on. When a person touches
the screen with a finger, the charge in the portion of the screen touched
discharges through the finger with a tiny spark. Electric current does not
normally flow through glass, so only the charge on that part of the screen
the finger touches is discharged. When cleaning a monitor, however, the
entire glass is wet and the charge on the entire screen will discharge to a
finger or hand causing a much more painful shock.
 |
Never allow any electrical-powered office equipment to become wet while
it is turned on, and never turn on any electronic equipment when it is wet.
Even when a computer is turned off for a few minutes, it is best not to
touch the monitor's CRT while handling or using other electronic
equipment-including the telephone. Wet or dry, a person may receive an
electric shock similar to one that can be received by touching a metallic
object when vacuuming, machining a dielectric, or walking across carpeting
in leather shoes.
|
| | |
NFPA Regulations for Fire and Lightning. NFPA 77 (Static Electricity)
contains requirements for reducing the fire hazard of static electricity.
Lightning, an example of static electricity, is covered in NFPA 780 (Lightning
Protection Code). This document gives lightning protection requirements for
ordinary facilities and for facilities containing flammable vapors, gases, or
liquids.
Flammable Vapor. A flammable vapor source can be ignited by static
electricity if the following conditions exist simultaneously:
 |
Generation of a static charge imbalance.
 |
Static charge accumulation.
 |
Flammable atmosphere.
 |
A spark with significant ignition energy or temperature.
|
| | |
Liquids. Electrostatic charges can be generated by the movement of
liquid through pipes, funnels, pumps, filters, or by free-flowing through air.
Static charges generated by flowing liquids can be reduced or eliminated by
bonding or grounding, or both; by lowering the flow rate; or by reducing the
amount of misting, spraying, free-fall, and splashing of the liquid. Pay
particular attention to situations where the liquid stream may impinge on a
connection to a capacitor, high-voltage bushing, or cable terminal. Static
charge from the liquid can store hazardous quantities of electrical energy in a
capacitor over time. This hazard is most likely to occur when filling electronic
apparatus tanks with insulating oil.
Personal protective equipment is required when installing, examining,
adjusting, servicing, fabricating, testing, or maintaining electrical equipment.
The work supervisor shall provide employees with the appropriate PPE, and shall
ensure that the equipment is used properly. Alternatively, employees may contact
the area ES&H Team for assistance in selecting the appropriate PPE for the
operation. Protective footwear; hard hats; and insulated, nonmetallic-framed
safety glasses shall meet the requirements of ANSI Z41, ANSI Z87.1, and ANSI
Z89.2 (see Table 1 below).
Rubber-insulated (nonconductive) protective equipment shall be visually
inspected at the beginning of each workday before use and after performing work
that can cause damage to PPE. This inspection shall include an air test of the
gloves used. Hot sticks, grounds, aerial-lift equipment and booms, hot rope, and
hot ladders shall also be visually inspected.
Major modifications to new and existing facilities and projects may be
inspected by the DOE (or authorized designee) to verify compliance with codes
and standards in effect on the day that such work is approved by a final design
review. If the modification involves a hazard to life, equipment, or property,
current safety requirements shall be reviewed and used to mitigate the hazard.
Table 1. ASTM/ANSI standards for PPE.
Protective equipment or apparel
|
ASTM
standard
|
ANSI
standard
|
Rubber, insulating gloves
|
D 120
|
--
|
Rubber, insulating matting
|
D 178
|
--
|
Rubber, insulating blankets
|
D 1048
|
--
|
Rubber, insulating covers
|
D 1049
|
--
|
Rubber, insulating line hose
|
D 1050
|
--
|
Rubber, insulating sleeves
|
D 1051
|
--
|
Protective foot wear
|
--
|
Z41
|
Eye and face protection
|
--
|
Z87.1
|
Nonconductive hard hats (helmets)
|
--
|
Z89.2
|
Leather protectors for rubber insulating gloves
|
F 696
|
--
|
Anyone who witnesses or discovers a serious electric shock that results in
any of the conditions listed below, at the Livermore site or at Site 300 shall
immediately call the Fire Department Emergency Rescue (dial 911) (from a
cell-phone, call 925-447-6880).
-
Obvious serious injury (e.g., loss of consciousness, significant
trauma).
-
Altered mental status (e.g., confusion, slow/slurred speech).
-
Other obvious injury (e.g., laceration, muscle strain, burn).
In addition to calling 911:
 |
Ensure that all potential sources of energy are safe and in a neutral
state, if you are qualified.
 |
Initiate cardiopulmonary resuscitation (CPR), if appropriate. (Only
trained personnel should perform this task.)
 |
Notify the victim's supervisor and the appropriate ES&H Team as soon
as possible. (The victim's supervisor and the Hazards Control Department
will want to determine what caused the electric shock.)
|
| |
Refer to
Document 10.1, "Occupational Medical Program," in the ES&H
Manual for additional information.
All other electric shock victims must be taken to the Health Services
Department for evaluation so that potentially damaging effects can be detected
early and treated properly. It should be noted that such effects may not be
immediately recognized and can appear later (see Appendix B
for details). Do not let the shock victim drive himself to the Health Services
Department.
 |
Notify the victim's supervisor and the appropriate ES&H Team as soon
as possible. (The victim's supervisor and the Hazards Control Department
will want to determine what caused the electric shock.)
|
Serious and potentially lethal incidents, including near misses that could
result in a serious or potentially lethal shock, shall undergo an incident
analysis in accordance with Document
4.5, "Incidents--Notification, Analysis, and Reporting," in the ES&H
Manual. This analysis shall be determined by facility or program management
and the responsible ES&H Team.
 |
Properly secure the area once the victim is under care, leaving items
and equipment in the same position as much as possible. Try to remember the
original position of items that may have been moved during response to the
accident.
 |
Record the time, date, and location of the accident; the name of the
victim and any witnesses; who was notified; the voltage and current; the
contact parts of the body; what equipment or system was being serviced; and
the shock reaction and duration of the shock.
|
|
Electrical Workers. Employees who perform electrical work shall be
trained to recognize the hazards associated with their work environment and use
appropriate procedures and protective equipment to minimize the risk of an
accident or injury. The payroll supervisor provides trained electrical workers.
Work supervisors shall verify the qualifications and training of all electrical
workers before they are permitted to perform electrical work. Training
requirements are identified in Document
40.1, "LLNL Training Program Manual," in the ES&H Manual
and the Directorate Training Implementation Plan.
Employee training shall be documented with respect to the specific equipment
and tasks for which the employee is qualified. Much of the experience required
for an employee to be considered qualified is specific to the equipment and
tasks involved. On-the-job training is always a necessary component of a
qualification program. Classroom training, including courses offered by the
Hazards Control Department, is a useful way to ensure that employees share a
common level of basic knowledge on which to build specific on-the-job training.
Additionally, employees can gain knowledge and experience about how to perform
their jobs safely and properly by taking courses offered by universities and
trade schools or through apprenticeships, on-the-job training (OJT), or other
formalized training. The depth of training and how training is provided shall be
determined by the hazards associated with the employee's respective tasks.
Electrical workers shall be trained in and familiar with the following
subject areas:
 |
The safety-related work practices required by 29 CFR 1910, Subparts
J and S;
and 29 CFR 1926, Subparts
K and V
(see Sections 5.0 and 6.3 for
details).
 |
Techniques necessary to de-energize electrical systems, identify live
parts of equipment, and determine the nominal voltage of exposed live parts
and clearance distances specified in Document
16.2.
 |
Procedures for locking out and tagging energized electrical circuits and
equipment safely. Document
12.6 contains specific details.
 |
Other subjects, such as
 |
Electrical Safety Requirements for Employee Workplaces (NFPA 70E).
 |
National Electrical Code (NFPA 70).
 |
National Electrical Safety Code (ANSI/IEEE C2).
 |
Use of personal protective grounds (29
CFR 1926.954(e)).
 |
Use of testing and measuring equipment (29
CFR 1910.334(c)).
 |
Safety plans and work authorization documents (IWS, FSPs and OSPs).
 |
Use and care of personal protective equipment (29
CFR 1910.335(a)).
 |
Hazard categories and personnel requirements.
 |
The requirements of this document.
|
| | | | | | | |
|
| | |
The Hazards Control Department offers the following courses to fulfill some
of these requirements:
 |
HS5210,
"Capacitor Safety Orientation"
 |
HS5230,
"High-Voltage Safety"
 |
HS5245,
"Lock and Tag Procedure"
 |
HS5250,
"Working on Energized R&D Equipment"
|
| | |
Refresher training for electrical workers is required at intervals listed in
the course catalog, and shall include a formal review of current regulations and
safety practices.
Electrical workers should take HS1620,
"Multimedia First Aid with CPR."
Nonelectrical Workers. The Occupational Safety and Health
Administration requires training for nonelectrical workers whose job assignments
require them to be close to exposed parts of electrical circuits operating at 50
V or more. The Hazards Control Department offers the following course for this
purpose:
 |
HS5220,
"Electrical Hazards Awareness"
|
In addition to the courses the Hazards Control Department offers, both
electrical and nonelectrical workers whose job assignment requires them to work
close to exposed electrical circuits operating at 50 V or more to ground (in
accordance
29 CFR 1910.332) should receive supplementary training in the following
subject areas:
 |
The proper handling of portable tools and appliance cords.
 |
Procedures for resetting overcurrent protective devices.
 |
Techniques for approaching distances to overhead conductors.
 |
The meaning of electrical safety warnings and barriers.
 |
Electrical hazards associated with water.
 |
The proper response to electric shock.
|
| | | | |
For additional training requirements, see the LLNL Training Program Manual
and the Directorate Training Implementation Plan.
All workers and organizations shall refer to Document
2.1, "Laboratory and ES&H Policies, General Worker
Responsibilities, and Integrated Safety Management," in the ES&H
Manual for a list of general responsibilities. This section describes
specific responsibilities of LLNL organizations and workers who have key safety
roles. The responsibilities of individuals with regard to electrical work are
listed below each title.
 |
Only perform the tasks for which you are qualified.
 |
Understand the basic principles of electricity and electrical safety.
 |
Follow applicable OSHA requirements.
 |
Use the proper tools and required PPE.
 |
Request additional training to avoid working beyond your level of
qualification or comfort.
 |
Comply with the requirements set forth by the DOE, OSHA, and LLNL.
|
| | | | |
 |
Ensure employees
 |
Comply with the requirements set forth by the DOE, OSHA, LLNL, and
other regulatory agencies.
 |
Have the appropriate PPE available and use them properly.
 |
Are adequately qualified to perform their jobs.
|
| |
 |
Determine the work each employee is qualified to perform and make work
assignments accordingly.
|
|
 |
Provide support primarily through the ES&H Teams, which are the
initial point-of-contact for all safety issues raised by Programs or
individuals.
 |
Identify electrical safety hazards and make recommendations for
resolution.
 |
Provide support to program line management responsible for analyzing
electrical accidents and incidents.
 |
Evaluate electrical accidents and incidents to determine trends.
 |
Develop, review, and approve electrical safety training programs.
 |
Interact on a continual basis with groups (e.g., ES&H Working Group
and subcommittees, Directorate safety committees and councils, the ES&H
Teams) charged with providing a safe work environment for employees. This
interaction may include conducting electrical safety presentations and
providing a forum (e.g., written or electronic communication or meetings)
for the exchange of ideas and information.
 |
Inform management and employees of lessons learned from electrical
accidents and incidents.
 |
Participate in DOE electrical safety programs (e.g., DOE and EFCOG
Electrical Safety Committees).
|
| | | | | | |
29
CFR 1910, Subpart J, "General Environmental Controls." (Section
1910.147, "The control of hazardous energy lockout/tagout,"
specifically applies.)
29
CFR 1910, Subpart R, "Special Industries." (Section 1910.269,
"Electrical power transmission, and distribution," specifically
applies.)
29
CFR 1910.137, "Electrical Protective Devices."
DOE M
440.1-1, DOE Explosives Safety Manual.
For additional information about the topics covered this document, contact
the following:
 |
Work supervisor-General electrical concerns
 |
Area ES&H Team industrial safety engineer-Specific concerns about
electrical safety
 |
Industrial Safety/Safety Programs Division-Institutional electrical
safety concerns
 |
Safety Training
|
| | |
For lessons learned specific to electrical work areas or electrical
equipment, refer to the following web site:
29
CFR 1926, Subpart V, "Power Transmission and Distribution" (latest
edition).
ANSI
C73, "American National Standard on Dimensions of Attachment
Plugs" [configuration tables for general-purpose nonlocking and locking
plugs and receptacles].
ANSI
C84.1, "For Electric Power Systems and Equipment-Voltage Ratings (60
Hz)."
ANSI/IEEE
Standard 18, "IEEE Standard for Shunt Power Capacitors."
ANSI/IEEE
80, "IEEE Guide for Safety in AC Substation Grounding."
ANSI/IEEE
C2, "National Electrical Safety Code" (latest edition)."
ANSI/ISA-S82.01,
.02, and .03, "Safety Standard for Electrical and Electronic Test,
Measuring, Controlling and Related Equipment."
ANSI
Z136.1, Section 7, "ANSI Standard for the Safe Use of Lasers"
[Subsection 7.4, "Electrical Hazards."]
Charles F. Dalziel, "Deleterious
Effects of Electric Shock," International Labour Office Meeting of
Experts on Electrical Accidents and Related Matter (October 1961).
Electronics Engineering Department, Grounding Guidelines: Practical
Examples for Power Systems at LLNL, Lawrence Livermore National Laboratory,
Livermore, CA (UCID-19752).
IEEE
450-IEEE, "Recommended Practice for Maintenance, Testing, and
Replacement of Large Lead Storage Batteries for Generating Stations and
Substations."
NFPA 70B, Electrical
Equipment Maintenance.
NFPA 70E, Electrical
Safety Requirements for Employee Workplaces (latest edition).
NFPA 75, Electronic
Computer/Data Processing Equipment.
NFPA 77, Recommended
Practice on Static Electricity.
NFPA
780, Lightning Protection Code (latest edition).
NFPA 79, Electrical
Standard for Industrial Machinery National Fire Protection Association
(interpretations of current NFPA 70).
NFPA 110, A-Stored
Electrical Energy Emergency and Standby Power Systems."

The following terms and acronyms are used in this document and the
supporting appendices.
-
Affected employee
-
Any employee (including subcontractors) whose job requires him/her to
operate or use a machine or work in an area where service or maintenance of
equipment is being performed.
-
ac
-
Alternating current.
-
ANSI
-
American National Standards Institute.
-
Authority having jurisdiction (AHJ)
-
An individual who interprets the requirements of all electrical codes
and standards such as the National Electrical Code (NFPA 70); the National
Electrical Safety Code (ANSI/IEEE C2); 29 CFR 1910, Subpart
S; 29 CFR 1926, Subparts K
and V;
and Document
16.3. This individual also approves electrical equipment, wiring
methods, electrical installations, and utilization of equipment for
compliance.
-
Authorized person
-
Any employee (including subcontractors) with acquired skills and
training who has been approved or assigned by the supervisor to perform
specific work or tasks.
-
Bonding
-
The permanent joining of metallic parts to form an electrically
conductive path that will ensure electrical continuity and the capacity to
conduct safely any current likely to be imposed.
-
CFR
-
Code of Federal Regulations.
-
Competent person
-
A person who is (1) capable of identifying existing and predictable
hazards in workplaces; and (2) authorized and qualified by management to
take prompt corrective measures to eliminate hazards, provide first aid, and
notify the appropriate personnel when an accident or incident occurs.
-
CPR
-
Cardiopulmonary resuscitation.
-
Dead-front construction
-
Electrical equipment built so that, in NEC 70 Article 100's definition,
it is "without live parts exposed to a person on the operating side of
the equipment." Article 384 (Switchboards and Panel Boards), in
paragraph 384-3.(a), requires that "barriers shall be placed in all
service switchboards that will isolate the service bussbars and terminals
from the remainder of the switchboard."
-
dc
-
Direct current.
-
Electrical equipment
-
A general term for material, fittings, devices, appliances, fixtures,
apparatus, and the like that are used as a part of or in connection with an
electrical installation. The term applies to both power-generation equipment
and electronics equipment.
-
Electrical hazard
-
Any situation in which an employee or any conductive tool or object in
contact with the employee could contact or approach closer than the safe
clearance distance of any live part or other energized conductor. Any
situation in which electrical equipment is likely to cause a fire because of
defective components or design. Examples of electrical hazards include
inadequate working clearance while working on energized circuits, exposed
energized parts, electrical equipment inadequately guarded or enclosed,
electrical equipment in an unsafe environment, and unsafe electrical
equipment. Generally, electrical equipment that is not in compliance with
OSHA regulations or NEC standards presents a potential hazard.
-
Electrical worker
-
An electrical worker is a person trained, qualified, and authorized to
work on electrical equipment. He/she is usually hired specifically for this
purpose.
-
Facility power
-
Main disconnects, panel boards, switches, and associated wiring are
considered facility/building power and are typically less than 600 V ac.
These systems are designed and installed to operate facilities in these
buildings (i.e., lighting, heating, air conditioning, or standby power
supply and circuitry).
-
FSP
-
Facility Safety Plan.
-
GFCI
-
Ground-fault circuit interrupter.
-
Grounded
-
Connected to earth or to some conducting body that serves in place of
the earth. Physically and intentionally connected to the earth through a
ground connection of sufficient low impedance and with sufficient
current-carrying capacity to prevent the buildup of voltages that may result
in undue hazard to connected equipment or persons. (See ungrounded.)
-
Joule (J)
-
Watt-second (power x time); a unit of energy.
-
Labeled
-
Equipment or materials to which a label, symbol, or other identifying
mark has been applied by an NRTL.
-
Listed
-
Equipment or materials included in a list published by an NRTL.
-
Live/energized parts
-
The current edition of 29 CFR 1910 defines a "live part" as an
electrically conducting part carrying more that 50 V ac or dc. (A part may
be designated as "not live" if the current from the part to ground
through 1500 ohms non-inductive resistance shunted by a capacitance of 0.15
µf cannot exceed 0.5 mA, even though the part carries voltage equal to or
greater than that specified for a live part.)
-
Lockout and tag procedure
-
LLNL's general procedure for affixing appropriate locks and tags to
energy-isolating devices to prevent inadvertent energizing or start-up of
machines or equipment while service and maintenance is being performed.
Lockout devices prevent the release of energy that could cause injury or
death. Refer to Document
12.6 for details on this procedure.
-
Minimum work distance or clearance
-
A minimum separation distance between a qualified electrical worker (or
any conducting object touching the worker) and any energized component.
Also, a mandatory separation distance between any energized component and
vehicles or machinery. See Document
16.2, 29
CFR 1910.303, and 29
CFR 1910.304.
-
NEC
-
National Electrical Code.
-
NEMA
-
National Electrical Manufacturers Association.
-
NFPA
-
National Fire Protection Association.
-
Nationally recognized testing Laboratory (NRTL)
-
An organization that is concerned with product evaluation and maintains
periodic inspection of listed equipment and materials. The NRTL ensures that
the equipment or materials meet appropriate designated standards and that
they have been tested and found to be suitable for use in a specified
manner. (Refer to 29
CFR 1910.7, "Definition and Requirements for a Nationally
Recognized Testing Laboratory.")
-
Nominal system voltage
-
A nominal value assigned to a circuit or system to conveniently
designate its voltage class (e.g., 120/240 V, 480Y/277 V, 600 V). The actual
voltage at which a circuit operates can vary from the nominal within a range
that permits satisfactory operation of the equipment. (Refer to ANSI C84.1,
"Electric Power Systems and Equipment--Voltage Ratings [60 Hz]"
for details.)
-
OJT
-
On-the-job training.
-
OSHA
-
Occupational Safety and Health Administration.
-
OSP
-
Operational Safety Plan.
-
PPE
-
Personal protective equipment.
-
Qualified person
-
A person who has been determined by his/her supervisor to have the
skills, knowledge, and abilities to safely perform the work to which he/she
is assigned. Qualifications may include a recognized degree, certificate, or
professional standing--through extensive knowledge, training, and
experience--or that one has successfully demonstrated the ability to resolve
problems relating to the subject matter or work to the satisfaction of
his/her supervisor.
-
Safety watch
-
A person specifically assigned to stand by (within visible and audible
range of workers) and continually monitor equipment and personnel for
safety.
-
Strain relief
-
A mechanical device that prevents force from being transmitted to the
connections or terminals of a cable.
-
Temporary wiring
-
Electrical wiring that is temporarily installed for a limited time to
complete a specific task (e.g., construction of a new facility or
performance of R&D work). Temporary wiring methods must apply sound
engineering practices to ensure adequate electrical safety of temporary
wiring installations. Temporary wiring shall conform to the requirements in Section
3.5 of this document, Article 305 of the NEC, and the respective
subparts of 29
CFR 1910 and 29
CFR 1926.
-
Ungrounded
-
A condition having no physical connection or continuity with earth
ground. A condition of insulation or isolation. (See grounded.)
-
Utility power
-
Utility, transmission, and distribution of electrical power systems
typically above 600 V ac (i.e., substations, vaults, transformers, switch
gear) prior to the final point of transformation and distribution. These
electrical systems and equipment then furnish electrical power to buildings
and facilities through an electric service entrance. Qualified Plant
Engineering personnel (or their designees) are the only individuals
authorized to work on these high-voltage systems.
-
Work supervisor
-
The person responsible for supervising and directing the work and
ensuring the health and safety of workers. Specific responsibilities include
 |
Understanding potential hazards of the work.
 |
Ensuring that an employee is qualified by knowledge, training, and
experience; that he/she has successfully demonstrated the ability to
safely complete the work; and that the employee is authorized to perform
the work.
 |
Having a complete understanding and the ability to reach agreement
with the qualified person about the work to be performed, the sequence
in which it should be done, and the potential and present hazards
involved--having outlined those hazards and/or limitations of tasks to
the extent considered necessary to ensure the worker's health and
safety.
|
| |

Electricity flowing through the human body can shock, cause involuntary
muscle reaction, paralyze muscles, burn tissues and organs, or kill. The typical
effects of various electric currents flowing through the body on the average
150-lb male and 115-lb female body are given in Table B-1.
Burns. Although a current may not pass through vital organs or nerve
centers, internal electrical burns can still occur. These burns, which are a
result of heat generated by current flowing in tissues, can be either at the
skin surface or in deeper layers (muscles, bones, etc.), or both. Typically,
tissues damaged from this type of electrical burn heal slowly.
Burns caused by electric arcs are similar to burns from high-temperature
sources. The temperature of an electric arc, which is in the range of
4,000-35,000°F, can melt all known materials, vaporize metal in close
proximity, and burn flesh and ignite clothing at distances up to 10 ft from the
arc.
Table B-1. Effects of electric current on the human body (Ref. 1).
Effect/feeling
|
Direct current
(mA)
|
Alternating current (mA)
|
Incident severity
|
60 Hz
|
10,000 Hz
|
150 lb
|
115 lb
|
150 lb
|
115 lb
|
150 lb
|
115 lb
|
Slight sensation
|
1
|
0.6
|
0.4
|
0.3
|
7
|
5
|
None
|
Perception threshold
|
5.2
|
3.5
|
1.1
|
0.7
|
12
|
8
|
None
|
Shock not painful
|
9
|
6
|
1.8
|
1.2
|
17
|
11
|
None
|
Shock painful
|
62
|
41
|
9
|
6
|
55
|
37
|
Spasm, indirect injury
|
Muscle clamps source
|
76
|
51
|
16
|
10.5
|
75
|
50
|
Possibly fatal
|
Respiratory arrest
|
170
|
109
|
30
|
19
|
180
|
95
|
Frequently fatal
|
>0.03-s vent. fibril.
|
1300
|
870
|
1000
|
670
|
1100
|
740
|
Probably fatal
|
>3-s vent. fibril.
|
500
|
370
|
100
|
67
|
500
|
340
|
Probably fatal
|
>5-s vent. fibril.
|
375
|
250
|
75
|
50
|
375
|
250
|
Probably fatal
|
Cardiac arrest
|
--
|
--
|
4000
|
4000
|
--
|
--
|
Possibly fatal
|
Organs burn
|
--
|
--
|
5000
|
5000
|
--
|
--
|
Fatal if it is a vital organ
|
Delayed Effects. Damage to internal tissues may not be apparent
immediately after contact with the current. Internal tissue swelling and edema
are also possible.
Critical Path. The critical path of electricity through the body is
through the chest cavity. At levels noted in Table B-1, current flowing from one
hand to the other, from a hand to the opposite foot, or from the head to either
foot will pass through the chest cavity paralyzing the respiratory or heart
muscles, initiating ventricular fibrillation and/or burning vital organs.
Influential Variables. The effects of electric current on the human
body can vary depending on the following:
 |
Source characteristics (current, frequency, and voltage of all electric
energy sources).
 |
Body impedance and the current's pathway through the body.
 |
How environmental conditions affect the body's contact resistance.
 |
Duration of the contact.
|
| | |
Source Characteristics. An alternating current (ac) with a voltage
potential greater than 550 V can puncture the skin and result in immediate
contact with the inner body resistance. A 110-V shock may or may not result in a
dangerous current, depending on the circuit path which may include the skin
resistance. A shock greater than 600 V will always result in very dangerous
current levels. The most severe result of an electrical shock is death.
Conditions for a serious (potentially lethal) shock across a critical path,
such as the heart, are
-
More than 30-V root mean square (rms), 42.4-V peak, or 60 V dc at a
total impedance of less than 5000 ohms.
-
10 to 75 mA.
-
More than 10 J.
Conditions for a potentially lethal shock across the heart are
-
More than 375 V at a total body impedance of less than 5000 ohms.
-
More than 75 mA.
-
More than 50 J.
The worst possible frequency for humans is 60 Hz, which is commonly used in
utility power systems. Humans are about five times more sensitive to 60-Hz
alternating current than to direct current. At 60 Hz, humans are more than six
times as sensitive to alternating current than at 5000 Hz--and the sensitivity
appears to decrease still further as the frequency increases. Above 100-200 kHz,
sensations change from tingling to warmth, although serious burns can occur from
higher radio-frequency energy.
At much higher frequencies (e.g., above 1 MHz), the body again becomes
sensitive to the effects of an alternating electric current, and contact with a
conductor is no longer necessary; energy is transferred to the body by means of
electromagnetic radiation (EMR). For a discussion on the effects of EMR and the
controls required for these sources, refer to
Document 20.7, "Nonionizing Radiation and Fields (Electromagnetic
Fields and Radiation with Frequencies Below 300 GHz," in the ES&H
Manual.
Body Impedance. Three components constitute body impedance: internal
body resistance and the two skin resistances at the contact points with two
surfaces of different voltage potential. One-hand (or single-point) body contact
with electrical circuits or equipment will prevent a person from completing a
circuit between two surfaces of different voltage potential. Table
B-2 provides a listing of skin-contact resistances encountered under various
conditions. It also shows the work area surfaces and wearing apparel effects on
the total resistance from the electrical power source to ground. This table can
be used to determine how electrical hazards could affect a worker in varying
situations.
Table B-2. Human resistance (Q) for various skin-contact conditions
(Ref. 2).
Body contact condition
|
Dry (ohms)
|
Wet (ohms)
|
Finger touch
|
40,000-1,000,000
|
4,000-15,000
|
Hand holding wire
|
15,000-50,000
|
3000-5000
|
Finger-thumb grasp
|
10,000-30,000
|
2000-5000
|
Hand holding a pliers
|
5000-10,000
|
1000-3000
|
Palm touch
|
3000-8000
|
1000-2000
|
Hand around 1.5-in. pipe or drill handle
|
1000-3000
|
500-1500
|
Two hands around 1.5-in. pipe
|
500-1500
|
250-750
|
Hand immersed
|
--
|
200-500
|
Foot immersed
|
--
|
100-300
|
Life-Threatening Effects. Charles F. Dalziel,1 Ralph H.
Lee,2 and others have established the following criteria for the
lethal effects of electric shock:
 |
Currents in excess of a human's "let-go" current (>16
mA at 60 Hz) passing through the chest can produce collapse,
unconsciousness, asphyxia, and even death (see also Table
B-1).
 |
Currents (>30 mA at 60 Hz) flowing through the nerve centers
that control breathing can produce respiratory inhibition, which could last
long after interruption of the current.
 |
Cardiac arrest can be caused by a current greater than or equal to 1 A
at 60 Hz flowing in the region of the heart.
 |
Relatively high currents (0.25-1 A) can produce fatal damage to the
central nervous system.
 |
Currents greater than 5 A can produce deep body and organ burns,
substantially raise body temperature, and cause immediate death.
 |
Delayed reactions and even death can be caused by serious burns or other
complications.
|
| | | | |
The most dangerous current flow via the chest cavity is through the heart
when the shock occurs in the time relative to the normal heart rhythm. This
current may cause ventricular fibrillation, which is defined as repeated, rapid,
uncoordinated contractions of the heart ventricles. Ventricular fibrillation
that alters the heart's normal rhythmic pumping action can be initiated by a
current flow of 75 mA or greater for 5 seconds (5-s) or more through the chest
cavity.
Probability of Ventricular Fibrillation. To determine the 5-s current flow
(in mA) necessary to cause a 0.5% probability of ventricular-fibrillation,
multiply a person's weight (in lb) by 0.49. To determine the 5-s current flow
(in mA) necessary to cause a 99.5% probability of ventricular fibrillation,
multiply a person's weight (in lb) by 1.47.
Use the information in Tables B-l through B-3 to project how electrical
hazards could affect a worker in varying situations when protective equipment
and apparel are in series with current flowing through a body. To determine how
much current, I, is passing along a body path, use the formula I = E/R. The
voltage, E, can be obtained using an appropriate voltmeter. The total body
resistance, R, can be determined by combining the appropriate resistance from
Table B-2 with that from Table B-3.
Table B-3. Resistance values for equal areas (130 cm2)
of
various work-area materials (Ref. 2).
Material
|
Resistance (Q)
|
Rubber gloves or soles
|
2.0 x 107
|
Dry concrete above grade
|
1.0 x 106 to 5.0 x 106
|
Dry concrete on grade
|
2.0 x 105 to 1.0 x 106
|
Leather sole, dry, including foot
|
1.0 x 105 to 5.0 x 105
|
Leather sole, damp, including foot
|
5.0 x 103 to 2.0 x 104
|
Wet concrete on grade
|
1.0 x 103 to 5.0 x 103
|
-
Charles F. Dalziel, "The Effects of Electric Shock on Man,"
Industrial Radio Engineers Transactions on Medical Electronics (May 1956).
-
Ralph H. Lee, "Human Electrical Sheet" while an IEEE Fellow at
E. I. duPont de Nemours & Co.; and "Electrical Safety in Industrial
Plants," in IEEE Spectrum, June 1971.
Here is another set of rules for electrical safety SOURCE:
NREL Electrical Safety Program
Provider: Environment, Safety & Health Office
Related ES&H Policy: Policy
6-4, Worker Safety and Health.
Last updated: July 1997
Document #: ESH 6-4.15

Table of Contents
I.
|
|
II.
|
|
III.
|
|
IV.
|
|
V.
|
|
VI.
|
|
|
|
A.
|
|
|
|
B.
|
|
|
|
C.
|
|
|
|
D.
|
|
|
|
E.
|
|
|
|
F.
|
|
|
|
G.
|
|
|
|
|
|
I. Purpose
-
The NREL Electrical Safety Program has been developed to ensure
the safety of all employees who work with or around electrical
equipment and distribution systems. Because of the diversity in
job assignments throughout the Laboratory, NREL employees are at
varying levels of potential exposure to energized components of
electrical systems.
-
The Electrical Safety Program addresses a variety of potential
exposure levels and describes precautionary measures that are to
be implemented to minimize risks.
II. Program Authorization
-
The NREL Electrical Safety Program provides specific details for
compliance with safety requirements established by Policy
6-4, Worker Safety and Health. All responsibilities, general
rules, and procedures from Policy 6-4 apply to this program.
-
This program applies to all electrical installations as well as
to work performed with or near electrical equipment and/or
distribution systems. Since electrical equipment is present in
office areas as well as laboratory areas, the program encompasses
all areas and activities at NREL. This program applies to everyone
performing work at NREL sites including, but not limited to;
permanent and temporary NREL employees, visiting professionals,
students, subcontractors, vendors, etc.
IV. References
 |
 |
NREL ES&H Inspection Program
 |
 |
NFPA 70, the "National Electrical Code" (NEC)
 |
NFPA 70E, "Electrical Safety Requirements for Employee
Workplaces"
 |
29 CFR 1910.147 "The Control of Hazardous Energy"
(Lockout/Tagout)
 |
29 CFR 1910.331-335 (OSHA) "Electrical Safety-Related Work
Practices"
|
| | | | | |
V. Definitions
-
Electrical Distribution System: Electrical components and
associated hardware, such as wall mounted switches, receptacles,
conduit, circuit breaker panels, etc. that are permanently
attached to buildings for the purpose of delivering electrical
power.
-
Electrical Exposure Levels: Risk levels of exposure to
energized electrical systems and components that employees face
while performing their daily job assignments. Three levels have
been identified. They are as follows:
-
Low: Employees with a low risk of potential exposure
to energized electrical components are managers, financial and
administrative support personnel, and other staff members who
primarily work in an office environment. Electrical equipment
in these areas is generally limited to 120 volt devices such
as; computers, printers, typewriters, space heaters, coffee
pots, extension cords, and other consumer electronics devices.
-
Moderate: Employees with moderate risk of potential
exposure to energized electrical systems are researchers,
engineers, technicians, machinists, copy center employees, and
other staff members who routinely work with or around
electrical or electromechanical equipment. Equipment used by
these employees may operate with voltages up to 600 volts.
These employees must be trained to recognize electrical
hazards and must be able to safely shut off power to the
equipment in the event of an emergency. Electrical equipment
used by these employees may include; power supplies, signal
generators, lasers, machining equipment, electric hand tools,
test equipment, etc.
-
High: Employees with the highest risk of potential
exposure to energized electrical components are electricians,
electrical engineers, maintenance technicians, and research
technicians who are responsible for maintenance, calibration,
installation, modifications, and set up of equipment and
electrical distribution systems. These employees may
periodically work on equipment or systems that require 480
volts or higher and shall be thoroughly trained in hazard
recognition, precautionary measures (including Lockout/Tagout
and the use of personal protective equipment [PPE]), and
emergency response procedures prior to beginning work on
electrical systems and equipment. Equipment may include;
electrical distribution systems, large electric motors,
heating-ventilation-and-air conditioning (HVAC) equipment,
uninterruptible power supplies (UPS), etc.
-
Energized Work: Any work performed on or close enough to
exposed parts of electrical circuits and equipment operating at
greater than 50 V to ground, or less than 50 volts to ground where
the current exceeds 5mA, and the potential for injury exists.
-
Journeyman Level Electrician: An individual who has
achieved a level of expertise in the electrical field and has
completed at least 4 years of apprentice level training and
hands-on experience. Formal trade school training and/or licensing
by the state generally accompany this level of expertise.
-
Lockout/Tagout: A procedure which ensures that all
hazardous energy sources are secured in a safe manner prior to any
servicing or maintenance activities. The NREL
Lockout/Tagout Program provides details of this procedure.
-
Safe Work Permit: A permit issued by the ES&H Office
or other authorized staff for hazardous activities including work
on energized electrical systems, as described in Policy 4-10,
Occupational Safety & Health.
-
Two Worker Rule: An NREL rule which requires that a
second worker be present whenever work is performed with or near
energized electrical systems. The second worker shall be trained
in emergency response procedures and shall be present only as an
observer, and must not participate in the actual work that is
being performed.
VI. Program Components & Assignments
-
All electrical installations and electrical practices at NREL
shall be performed in compliance with the reference standards
identified in Section IV of this program.
-
-
The NREL Electrical Safety Program is comprised of six
primary elements which are supported by various NREL
ES&H programs, as follows:
-
Policies & Procedures, and Programs:
Various Policies/Procedures have been developed and
implemented at NREL to ensure safe work practices by
employees and safe working conditions. The parent
document to this program is the NREL Policy 4-10,
Occupational Safety and Health (OSH) which describes
individual and line management responsibilities
necessary for the implementation of an effective
Electrical Safety Program.
Another relevant subdocument to the OSH
Policy/Procedure is the NREL
Lockout/Tagout Program which has been
implemented to ensure that equipment is deenergized
and securely isolated from external and internal
energy sources, prior to operations such as
maintenance activities, in which the accidental
startup or release of energy could cause injury.
This Electrical Safety Program shall be used
in conjunction with the above referenced documents.
-
Safe Operating Procedures (SOP): Laboratory
or project specific SOPs shall be developed and
maintained which identify electrical hazards and
prescribe precautionary measures which must be in
place for specific research and maintenance
activities. Additionally, SOPs must include specific
information on energized work and/or Lockout/Tagout
procedures for equipment covered under the SOP. These
procedures must address multiple energy sources and
the capacity for stored or residual energy, if
present. SOPs are discussed in detail in NREL Policy
4-4, Risk Assessment
-
Training: Electrical Safety and Lockout/Tagout
training shall be provided for NREL employees on a
continuing basis. Subsection G further details
training requirements.
-
Inspections: Inspections shall be conducted
at regular intervals by qualified individuals to
identify electrical deficiencies in all occupied areas
serviced by electrical power. These inspections may be
performed as a part of or in conjunction with Center
safety inspections as described in the ES&H
Inspection Program.
-
Pre-Use - Fabricated Equipment -
Equipment inspections are required for equipment
such as specialized electrical devices fabricated
at NREL or at other facilities such as a
university or another laboratory. To ensure
electrical integrity, fabricated devices must be
inspected by a qualified staff member of Site
Operations, the ES&H Office, or by a member of
the NREL Electrical Safety Panel before being
used. No inspection is required for commercially
available devices that have been tested and
approved by a reputable testing laboratory such as
Underwriters Laboratories (UL), Factory Mutual
(FM), or Canadian Standards Association (CSA) and
are being used in unmodified form.
-
Periodic - Inspections shall be conducted at
regular intervals by qualified individuals to
identify electrical deficiencies in all occupied
areas serviced by electrical power. These
inspections may be performed as part of or in
conjunction with Center level safety inspections
as described in the ES&H Inspection Program.
-
Personal Protective Equipment (PPE): PPE
including non-conductive head gear, insulated shoes,
and eye and face protection, shall be made available
by NREL for use by all employees who work with or near
electrical equipment. Non-NREL employees (i.e.
contractors) are responsible for providing their own
PPE. The use of PPE is presented in NREL Policy 4-3,
Personal Protective Equipment.
-
Guarding and Shielding Techniques: Protective
guards and shields which prevent individuals from
coming in contact with energized electrical components
shall be installed on all equipment and distribution
systems.
-
-
Included as Appendix A
of this program is an Electrical Safety Inspection
Guideline/Checklist developed by the NREL Electrical
Safety Panel. This checklist serves as a quick reference
to fourteen commonly found safety issues. Note: This
checklist does not cover all electrical safety concerns.
The National Electrical Code should be referenced for
specific details and more complete information regarding
electrical installations.
-
The DOE Electrical Safety Guidelines (October
1994) is a document that has been prepared by the DOE
Electrical Safety Committee and is to be used by DOE and
subcontractor personnel. The guidelines describe best
management practices and encompass the applications of
electrical safety requirements, standards, and regulations
including OSHA, NEC, and the National Electric Safety Code
(ANSI C2). The Table of Contents for the document is
included as Appendix B of this
program. The guidelines document is available from the
ES&H Office or the Site Operations Center.
-
The DOE Electrical Safety Guidelines for Research and
Development (DOD/ID-10600) are recognized best
management practices and apply to NREL operations. This
section contains safety criteria for the design,
fabrication, modification, installation, inspection,
testing, operation, and maintenance of R&D electrical
apparatus.
-
Design Requirements
-
General - In addition to complying with the
NEC, all facilities and equipment designs, installations,
and modifications must also conform to DOE 6430.1B, "General
Design Criteri"a. For many types of
installations, this order requires additional safety
measures that are more stringent than the NEC. For
example, the General Design Criteria requires that an
independent ground wire be used in all metallic raceways
in electrical distribution systems. These raceways cannot
serve as the sole ground path as allowed by the NEC.
Copies of this Order are available for reference from the
ES&H Office and Site Operations.
-
Commercially Available Equipment - This equipment must
bear the approval of a recognized testing laboratory such
as UL, FM, or CSA.
-
NREL Fabricated Equipment - Listed components shall be
used where available and the design shall comply with the
general requirements (i.e. NEC, etc.).
-
Vendor Fabricated Equipment - Listed components shall be
used where available and certification is required from
the manufacturer that the equipment complies with NEC,
etc. Certification requirements should be included in the
purchasing documents (i.e., statement of work, contract
specifications, etc.).
-
Foreign Manufactured/Fabricated Equipment - The Supplier
of foreign manufactured equipment will have to provide
documentation that demonstrates "equivalency"
with the requirements of the NEC or corresponding
guidelines established by nationally recognized testing
laboratories (UL/CSA, etc.). The end user will be required
to provide the equivalency certification during the
pre-use inspection.
-
Facilities - Site Operations shall review installations
requiring moderate to large power demand (i.e., those
requiring a disconnect switch) to ensure that adequate
power is available.
-
-
Installations and modifications of building
electrical systems shall only be performed by
qualified journeyman level electricians. Installations are
to be performed by the Site Operations or by a qualified
contractor whose work has been authorized by the Site
Operations. Exception: Research Center staff
members may be allowed to work on or modify building
electrical systems if they are qualified to safely perform
the level of work to which they are assigned, and are
working under the approval and direct oversight of the
Site Operations Center. Electrical installations
performed by contractors and research staff members must
be inspected and approved by the Site Operations Center
before connection is made to the building electrical
system.
-
Equipment installations which are hard wired must
be installed with a readily accessible lockable disconnect
switch that is capable of isolating the input electrical
energy source. For equipment that is equipped with a power
cord and plug combination, the plug will serve as an
acceptable disconnecting means.
Receptacles that are located within six feet of sinks,
open sources of water, or in potentially wet locations
must be protected a by Ground Fault Circuit Interrupter
(GFCI).
-
Research equipment installations and electrical
connections shall be subjected to approval before
being placed into service. The approval process is
normally accomplished during required Readiness
Verifications (RV), as described in Policy 4-4, Risk
Assessment.
-
-
Site Operations is responsible for maintaining
and modifying the building electrical distribution
systems. Only those employees who have completed a
Journeyman level of expertise in the electrical trade (see
definition) will be allowed to work on electrical
distribution systems without direct supervision.
Apprentice employees who have not yet completed the
required four years of experience/educational requirements
may be allowed to work on distribution systems under the
direct supervision of a Journeyman level staff member.
-
Center Directors and Team Leaders have the
responsibility of ensuring that each employee under
his/her direction is qualified to safely perform the level
of work to which they are assigned. Following is a generic
description of NREL positions and a corresponding
explanation of the electrical work in which employees in
these positions are allowed to perform:
Electrician/Senior Maintenance Technician: Once
the appropriate level of expertise has been demonstrated
to their supervisor, these employees will be allowed to
work on electrical distribution systems. Due to the nature
of their work, these employees potentially have a High
electrical exposure level, as defined in Section V.
Therefore, these employees must have advanced training in
hazard recognition, and electrical safety principles.
General Maintenance Employees and Maintenance
Apprentices: While working under the direct
supervision of a Journeyman level technician, these
employees will be allowed to work on electrical
distribution systems.
Employees working at Researcher/Research Technician and
General Maintenance and Apprentice levels potentially have
a Moderate electrical exposure level as defined in Section
V, and are required to complete electrical safety
training.
Researchers/Research Technicians: Once the
appropriate level of competence has been demonstrated to
their Team Leader, these employees will be allowed to
perform electrical work on research apparatus and
associated equipment. However, these employees are
prohibited from working on facility electrical
distribution systems.
Exceptions: Qualified researchers and research
technicians may be allowed to work on electrical
distribution systems when the work involved is part of a
research project and the work has been approved by Site
Operations.
-
-
Work on energized systems that incorporate hazardous
circuits shall be strenuously avoided. A hazardous circuit
is defined as one operating at greater that 50 Volts, or
operating a 50 Volts or less with a current greater that 5
mA, or a hazardous energy level exceeding 10 joules. This
includes the maintenance and repair of research equipment.
This applies to both NREL employees and
contractors/vendors. When it cannot be avoided, only
qualified personnel who have been trained to work safely
on energized circuits shall perform the work.
-
If an experimental process or a research activity
requires employees to routinely work near or with
unshielded energized electrical components, the hazard and
precautionary measures must be addressed in the SOP. If
the exposure is an isolated occurrence, and the employee
has not achieved a journeyman level status, a Safe Work
Permit issued by the ES&H Office shall be obtained
before the start of work. Individuals performing these
tasks must adhere to safety-related work practices at all
times to prevent electric shock or other electrically
induced injuries.
-
The following safe work practices must be adhered to
when working with energized systems:
-
Exception: Taking voltage and current measurements
using standard test equipment such as voltmeters and
current probes is not considered performing work on
energized systems.
-
Two Worker Rule: Two persons must
always be present whenever work is performed on an
energized system. One person must be assigned as a
safety watch and will not participate in the actual
work being performed. The safety watch must be within
sight and hearing from the person performing the
electrical work (less than 50 feet) and must be
trained in emergency response procedures including
CPR.
-
Personal Protective Equipment (PPE): Workers
must wear appropriate PPE including rubber soled
shoes, Class "O" gloves, protective eyewear
and headgear if necessary, and use insulated hand
tools.
-
Preplanning and Safety: Before work begins,
the sequence of events for the project should be
planned, and appropriate written safety procedures
should be established.
-
Tools and Equipment: All tools that will be
required for the job should be readily available and
inspected to ensure that they are in good working
order. Only qualified workers shall operate tools and
equipment.
-
Posted Warnings and Barricades: Safety signs
shall be posted to warn other employees of potential
electrical hazards. In addition, barricades will be
used when necessary to limit access to work areas
where there is a potential for contact with exposed or
uninsulated energized conductors.
-
Restricted Work Area: The immediate work area
shall be restricted to authorized and qualified
workers.
-
Work Stoppage: If unsafe conditions develop
during the work process, the work shall be suspended
and the Center Director and Team Leader must be
immediately notified.
-
-
Employees shall be trained in and be familiar with
safety-related work practices that pertain to their
respective job assignments.
-
For those employees who fall within the
High and Moderate electrical exposure levels as
defined in Section V, Electrical Safety Training shall
be completed prior to starting work and at least every
three years.
-
Training will be optional for employees with Low
electrical exposure levels.
-
The training shall be provided by the NREL ES&H
Office and scheduled by Human Resources on a regular
basis.
-
Additional specialty training may be required for
employees in the High electrical exposure level, as
determined by their Team Leader. This training shall
be provided by qualified organizations outside NREL.
Electrical Safety Inspection Guidelines/Checklist
-
A 36 inch clearance must be maintained in front of all
electrical panels. (area is usually marked by striped black and
yellow tape)
-
Note any missing covers for electrical devices. (junction boxes,
receptacles, switches, etc.)
-
Ensure that flexible cords do not protrude through walls,
ceiling tiles, windows, or doors.
-
Ensure that flexible cords are not attached to walls or piping.
-
Note missing or improperly installed flexible cord connectors.
(area where cord is attached to device)
-
Inspect ground plugs on extension cords and portable electric
tools.
-
Inspect condition of flexible cords. (covering cracked, cut, or
otherwise physically damaged)
-
Note open or exposed terminal connections.
-
Note any exposed wiring.
-
Ensure that extension cords are properly sized with respect to
length and load capacity.
-
Multi-outlet strips must have overcurrent protection. (circuit
breaker)
-
Circuit breaker panels must have an updated schedule in place
identifying the circuit that each breaker controls.
-
Electrical cords and equipment should not be located near (or
inside of) sinks or other water sources unless a ground fault
circuit interrupter (GFCI) protects them.
-
Insure that any equipment undergoing repairs or maintenance work
is properly locked/tagged out.
Table of Contents for
DOE Electrical Safety Guidelines
May 1993
1.0
|
Introduction
|
2.0
|
General Requirements
|
3.0
|
Electrical Preventive Maintenance
|
4.0
|
Grounding
|
5.0
|
Special Occupancies
|
6.0
|
Requirements For Specific Equipment
|
7.0
|
High-Voltage Work In Excess of 600 Volts
|
8.0
|
Temporary Wiring
|
9.0
|
References
|
Appendix A
|
Understanding Electrical Safety
|
Appendix B
|
Definition Of Terms
|
Appendix C
|
Work Matrices
|
DOE Electrical Safety
Guidelines
October 3, 1994
|
10.0
|
Research and Development (Proposed New Section)
|
Note: These documents are available in the ES&H Office and
the Site Operations Center.
|
|
|
Use this search box to find specific information you seek.
Click on these electricianeducation.com links for more pages on this site about
electrician safety.
Click HERE to return to ElectricianEducation.com
Home Page.
|