Electric Transformers
Transformer Theory in detail - SOURCE
TRANSFORMERS

Mutual inductance and basic operation
Suppose we were to wrap a coil of insulated wire around a loop of
ferromagnetic material and energize this coil with an AC voltage source:

As an inductor, we would expect this iron-core coil to oppose the applied
voltage with its inductive reactance, limiting current through the coil as
predicted by the equations XL = 2πfL and I=E/X (or I=E/Z). For
the purposes of this example, though, we need to take a more detailed look at
the interactions of voltage, current, and magnetic flux in the device.
Kirchhoff's voltage law describes how the algebraic sum of all voltages in a
loop must equal zero. In this example, we could apply this fundamental law of
electricity to describe the respective voltages of the source and of the
inductor coil. Here, as in any one-source, one-load circuit, the voltage dropped
across the load must equal the voltage supplied by the source, assuming zero
voltage dropped along the resistance of any connecting wires. In other words,
the load (inductor coil) must produce an opposing voltage equal in magnitude to
the source, in order that it may balance against the source voltage and produce
an algebraic loop voltage sum of zero. From where does this opposing voltage
arise? If the load were a resistor, the opposing voltage would originate from
the "friction" of electrons flowing through the resistance of the
resistor. With a perfect inductor (no resistance in the coil wire), the opposing
voltage comes from another mechanism: the reaction to a changing magnetic
flux in the iron core.
Michael Faraday discovered the mathematical relationship between magnetic
flux (Φ) and induced voltage with this equation:

The instantaneous voltage (voltage dropped at any instant in time) across a
wire coil is equal to the number of turns of that coil around the core (N)
multiplied by the instantaneous rate-of-change in magnetic flux (dΦ/dt)
linking with the coil. Graphed, this shows itself as a set of sine waves
(assuming a sinusoidal voltage source), the flux wave 90o lagging
behind the voltage wave:

Magnetic flux through a ferromagnetic material is analogous to current
through a conductor: it must be motivated by some force in order to occur. In
electric circuits, this motivating force is voltage (a.k.a. electromotive force,
or EMF). In magnetic "circuits," this motivating force is magnetomotive
force, or mmf. Magnetomotive force (mmf) and magnetic flux (Φ)
are related to each other by a property of magnetic materials known as reluctance
(the latter quantity symbolized by a strange-looking letter "R"):

In our example, the mmf required to produce this changing magnetic flux (Φ)
must be supplied by a changing current through the coil. Magnetomotive force
generated by an electromagnet coil is equal to the amount of current through
that coil (in amps) multiplied by the number of turns of that coil around the
core (the SI unit for mmf is the amp-turn). Because the mathematical
relationship between magnetic flux and mmf is directly proportional, and because
the mathematical relationship between mmf and current is also directly
proportional (no rates-of-change present in either equation), the current
through the coil will be in-phase with the flux wave:

This is why alternating current through an inductor lags the applied voltage
waveform by 90o: because that is what is required to produce a
changing magnetic flux whose rate-of-change produces an opposing voltage
in-phase with the applied voltage. Due to its function in providing magnetizing
force (mmf) for the core, this current is sometimes referred to as the magnetizing
current.
It should be mentioned that the current through an iron-core inductor is not
perfectly sinusoidal (sine-wave shaped), due to the nonlinear B/H magnetization
curve of iron. In fact, if the inductor is cheaply built, using as little iron
as possible, the magnetic flux density might reach high levels (approaching
saturation), resulting in a magnetizing current waveform that looks something
like this:

When a ferromagnetic material approaches magnetic flux saturation,
disproportionately greater levels of magnetic field force (mmf) are required to
deliver equal increases in magnetic field flux (Φ). Because mmf is
proportional to current through the magnetizing coil (mmf = NI, where
"N" is the number of turns of wire in the coil and "I" is
the current through it), the large increases of mmf required to supply the
needed increases in flux results in large increases in coil current. Thus, coil
current increases dramatically at the peaks in order to maintain a flux waveform
that isn't distorted, accounting for the bell-shaped half-cycles of the current
waveform in the above plot.
The situation is further complicated by energy losses within the iron core.
The effects of hysteresis and eddy currents conspire to further distort and
complicate the current waveform, making it even less sinusoidal and altering its
phase to be lagging slightly less than 90o behind the applied voltage
waveform. This coil current resulting from the sum total of all magnetic effects
in the core (dΦ/dt magnetization plus hysteresis losses, eddy current
losses, etc.) is called the exciting current. The distortion of an
iron-core inductor's exciting current may be minimized if it is designed for and
operated at very low flux densities. Generally speaking, this requires a core
with large cross-sectional area, which tends to make the inductor bulky and
expensive. For the sake of simplicity, though, we'll assume that our example
core is far from saturation and free from all losses, resulting in a perfectly
sinusoidal exciting current.
As we've seen already in the inductors chapter, having a current waveform 90o
out of phase with the voltage waveform creates a condition where power is
alternately absorbed and returned to the circuit by the inductor. If the
inductor is perfect (no wire resistance, no magnetic core losses, etc.), it will
dissipate zero power.
Let us now consider the same inductor device, except this time with a second
coil wrapped around the same iron core. The first coil will be labeled the primary
coil, while the second will be labeled the secondary:

If this secondary coil experiences the same magnetic flux change as the
primary (which it should, assuming perfect containment of the magnetic flux
through the common core), and has the same number of turns around the core, a
voltage of equal magnitude and phase to the applied voltage will be induced
along its length. In the following graph, the induced voltage waveform is drawn
slightly smaller than the source voltage waveform simply to distinguish one from
the other:

This effect is called mutual inductance: the induction of a voltage
in one coil in response to a change in current in the other coil. Like normal
(self-) inductance, it is measured in the unit of Henrys, but unlike normal
inductance it is symbolized by the capital letter "M" rather than the
letter "L":

No current will exist in the secondary coil, since it is open-circuited.
However, if we connect a load resistor to it, an alternating current will go
through the coil, in phase with the induced voltage (because the voltage across
a resistor and the current through it are always in phase with each
other).

At first, one might expect this secondary coil current to cause additional
magnetic flux in the core. In fact, it does not. If more flux were induced in
the core, it would cause more voltage to be induced voltage in the primary coil
(remember that e = dΦ/dt). This cannot happen, because the primary coil's
induced voltage must remain at the same magnitude and phase in order to balance
with the applied voltage, in accordance with Kirchhoff's voltage law.
Consequently, the magnetic flux in the core cannot be affected by secondary coil
current. However, what does change is the amount of mmf in the magnetic
circuit.
Magnetomotive force is produced any time electrons move through a wire.
Usually, this mmf is accompanied by magnetic flux, in accordance with the mmf=ΦR
"magnetic Ohm's Law" equation. In this case, though, additional flux
is not permitted, so the only way the secondary coil's mmf may exist is if a
counteracting mmf is generated by the primary coil, of equal magnitude and
opposite phase. Indeed, this is what happens, an alternating current forming in
the primary coil -- 180o out of phase with the secondary coil's
current -- to generate this counteracting mmf and prevent additional core flux.
Polarity marks and current direction arrows have been added to the illustration
to clarify phase relations:

If you find this process a bit confusing, do not worry. Transformer dynamics
is a complex subject. What is important to understand is this: when an AC
voltage is applied to the primary coil, it creates a magnetic flux in the core,
which induces AC voltage in the secondary coil in-phase with the source voltage.
Any current drawn through the secondary coil to power a load induces a
corresponding current in the primary coil, drawing current from the source.
Notice how the primary coil is behaving as a load with respect to the AC
voltage source, and how the secondary coil is behaving as a source with respect
to the resistor. Rather than energy merely being alternately absorbed and
returned the primary coil circuit, energy is now being coupled to the
secondary coil where it is delivered to a dissipative (energy-consuming) load.
As far as the source "knows," it's directly powering the resistor. Of
course, there is also an additional primary coil current lagging the applied
voltage by 90o, just enough to magnetize the core to create the
necessary voltage for balancing against the source (the exciting current).
We call this type of device a transformer, because it transforms
electrical energy into magnetic energy, then back into electrical energy again.
Because its operation depends on electromagnetic induction between two
stationary coils and a magnetic flux of changing magnitude and
"polarity," transformers are necessarily AC devices. Its schematic
symbol looks like two inductors (coils) sharing the same magnetic core:

The two inductor coils are easily distinguished in the above symbol. The
pair of vertical lines represent an iron core common to both inductors. While
many transformers have ferromagnetic core materials, there are some that do not,
their constituent inductors being magnetically linked together through the air.
The following photograph shows a power transformer of the type used in
gas-discharge lighting. Here, the two inductor coils can be clearly seen, wound
around an iron core. While most transformer designs enclose the coils and core
in a metal frame for protection, this particular transformer is open for viewing
and so serves its illustrative purpose well:

Both coils of wire can be seen here with copper-colored varnish insulation.
The top coil is larger than the bottom coil, having a greater number of
"turns" around the core. In transformers, the inductor coils are often
referred to as windings, in reference to the manufacturing process where
wire is wound around the core material. As modeled in our initial
example, the powered inductor of a transformer is called the primary
winding, while the unpowered coil is called the secondary winding.
In the next photograph, a transformer is shown cut in half, exposing the
cross-section of the iron core as well as both windings. Like the transformer
shown previously, this unit also utilizes primary and secondary windings of
differing turn counts. The wire gauge can also be seen to differ between primary
and secondary windings. The reason for this disparity in wire gauge will be made
clear in the next section of this chapter. Additionally, the iron core can be
seen in this photograph to be made of many thin sheets (laminations) rather than
a solid piece. The reason for this will also be explained in a later section of
this chapter.

It is easy to demonstrate simple transformer action using SPICE, setting up
the primary and secondary windings of the simulated transformer as a pair of
"mutual" inductors. The coefficient of magnetic field coupling is
given at the end of the "k" line in the SPICE circuit
description, this example being set very nearly at perfection (1.000). This
coefficient describes how closely "linked" the two inductors are,
magnetically. The better these two inductors are magnetically coupled, the more
efficient the energy transfer between them should be.

transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 100
l2 3 5 100
** This line tells SPICE that the two inductors
** l1 and l2 are magnetically "linked" together
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 1k
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
Note: the Rbogus resistors are required to satisfy certain quirks
of SPICE. The first breaks the otherwise continuous loop between the voltage
source and L1 which would not be permitted by SPICE. The second
provides a path to ground (node 0) from the secondary circuit, necessary because
SPICE cannot function with any ungrounded circuits.
freq
v(2)
i(v1)
6.000E+01 1.000E+01 9.975E-03
Primary winding
freq
v(3,5) i(vi1)
6.000E+01 9.962E+00 9.962E-03
Secondary winding
Note that with equal inductances for both windings (100 Henrys each), the AC
voltages and currents are nearly equal for the two. The difference between
primary and secondary currents is the magnetizing current spoken of earlier: the
90o lagging current necessary to magnetize the core. As is seen here,
it is usually very small compared to primary current induced by the load, and so
the primary and secondary currents are almost equal. What you are seeing here is
quite typical of transformer efficiency. Anything less than 95% efficiency is
considered poor for modern power transformer designs, and this transfer of power
occurs with no moving parts or other components subject to wear.
If we decrease the load resistance so as to draw more current with the same
amount of voltage, we see that the current through the primary winding increases
in response. Even though the AC power source is not directly connected to the
load resistance (rather, it is electromagnetically "coupled"), the
amount of current drawn from the source will be almost the same as the amount of
current that would be drawn if the load were directly connected to the source.
Take a close look at the next two SPICE simulations, showing what happens with
different values of load resistors:
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 100
l2 3 5 100
k l1 l2 0.999
vi1 3 4 ac 0
** Note load resistance value of 200 ohms
rload 4 5 200
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01 4.679E-02
freq
v(3,5) i(vi1)
6.000E+01 9.348E+00 4.674E-02
Notice how the primary current closely follows the secondary current. In our
first simulation, both currents were approximately 10 mA, but now they are both
around 47 mA. In this second simulation, the two currents are closer to
equality, because the magnetizing current remains the same as before while the
load current has increased. Note also how the secondary voltage has decreased
some with the heavier (greater current) load. Let's try another simulation with
an even lower value of load resistance (15 Ω):
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 100
l2 3 5 100
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 15
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01 1.301E-01
freq
v(3,5) i(vi1)
6.000E+01 1.950E+00 1.300E-01
Our load current is now 0.13 amps, or 130 mA, which is substantially higher
than the last time. The primary current is very close to being the same, but
notice how the secondary voltage has fallen well below the primary voltage (1.95
volts versus 10 volts at the primary). The reason for this is an imperfection in
our transformer design: because the primary and secondary inductances aren't perfectly
linked (a k factor of 0.999 instead of 1.000) there is
"stray" or "leakage" inductance. In other words, some
of the magnetic field isn't linking with the secondary coil, and thus cannot
couple energy to it:

Consequently, this "leakage" flux merely stores and returns energy
to the source circuit via self-inductance, effectively acting as a series
impedance in both primary and secondary circuits. Voltage gets dropped across
this series impedance, resulting in a reduced load voltage: voltage across the
load "sags" as load current increases.

If we change the transformer design to have better magnetic coupling between
the primary and secondary coils, the figures for voltage between primary and
secondary windings will be much closer to equality again:
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 100
l2 3 5 100
** Coupling factor = 0.99999 instead of 0.999
k l1 l2 0.99999
vi1 3 4 ac 0
rload 4 5 15
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01 6.658E-01
freq
v(3,5) i(vi1)
6.000E+01 9.987E+00 6.658E-01
Here we see that our secondary voltage is back to being equal with the
primary, and the secondary current is equal to the primary current as well.
Unfortunately, building a real transformer with coupling this complete is very
difficult. A compromise solution is to design both primary and secondary coils
with less inductance, the strategy being that less inductance overall leads to
less "leakage" inductance to cause trouble, for any given degree of
magnetic coupling inefficiency. This results in a load voltage that is closer to
ideal with the same (heavy) load and the same coupling factor:
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
** inductance = 1 henry instead of 100 henrys
l1 2 0 1
l2 3 5 1
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 15
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01 6.664E-01
freq
v(3,5) i(vi1)
6.000E+01 9.977E+00 6.652E-01
Simply by using primary and secondary coils of less inductance, the load
voltage for this heavy load has been brought back up to nearly ideal levels
(9.977 volts). At this point, one might ask, "If less inductance is all
that's needed to achieve near-ideal performance under heavy load, then why worry
about coupling efficiency at all? If it's impossible to build a transformer with
perfect coupling, but easy to design coils with low inductance, then why not
just build all transformers with low-inductance coils and have excellent
efficiency even with poor magnetic coupling?"
The answer to this question is found in another simulation: the same
low-inductance transformer, but this time with a lighter load (1 kΩ instead
of 15 Ω):
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 1
l2 3 5 1
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 1k
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01 2.835E-02
freq
v(3,5) i(vi1)
6.000E+01 9.990E+00 9.990E-03
With lower winding inductances, the primary and secondary voltages are
closer to being equal, but the primary and secondary currents are not. In this
particular case, the primary current is 28.35 mA while the secondary current is
only 9.990 mA: almost three times as much current in the primary as the
secondary. Why is this? With less inductance in the primary winding, there is
less inductive reactance, and consequently a much larger magnetizing current. A
substantial amount of the current through the primary winding merely works to
magnetize the core rather than transfer useful energy to the secondary
winding and load.
An ideal transformer with identical primary and secondary windings would
manifest equal voltage and current in both sets of windings for any load
condition. In a perfect world, transformers would transfer electrical power from
primary to secondary as smoothly as though the load were directly connected to
the primary power source, with no transformer there at all. However, you can see
this ideal goal can only be met if there is perfect coupling of magnetic
flux between primary and secondary windings. Being that this is impossible to
achieve, transformers must be designed to operate within certain expected ranges
of voltages and loads in order to perform as close to ideal as possible. For
now, the most important thing to keep in mind is a transformer's basic operating
principle: the transfer of power from the primary to the secondary circuit via
electromagnetic coupling.
 |
REVIEW:
 |
Mutual inductance is where the magnetic flux of two or more
inductors are "linked" so that voltage is induced in one coil
proportional to the rate-of-change of current in another.
 |
A transformer is a device made of two or more inductors, one of
which is powered by AC, inducing an AC voltage across the second inductor.
If the second inductor is connected to a load, power will be
electromagnetically coupled from the first inductor's power source to that
load.
 |
The powered inductor in a transformer is called the primary winding.
The unpowered inductor in a transformer is called the secondary winding.
 |
Magnetic flux in the core (Φ) lags 90o behind the source
voltage waveform. The current drawn by the primary coil from the source to
produce this flux is called the magnetizing current, and it also lags
the supply voltage by 90o.
 |
Total primary current in an unloaded transformer is called the exciting
current, and is comprised of magnetizing current plus any additional
current necessary to overcome core losses. It is never perfectly sinusoidal
in a real transformer, but may be made more so if the transformer is
designed and operated so that magnetic flux density is kept to a minimum.
 |
Core flux induces a voltage in any coil wrapped around the core. The
induces voltage(s) are ideally in phase with the primary winding source
voltage and share the same waveshape.
 |
Any current drawn through the secondary winding by a load will be
"reflected" to the primary winding and drawn from the voltage
source, as if the source were directly powering a similar load.
|
| | | | | | |

Step-up and step-down transformers
So far, we've observed simulations of transformers where the primary and
secondary windings were of identical inductance, giving approximately equal
voltage and current levels in both circuits. Equality of voltage and current
between the primary and secondary sides of a transformer, however, is not the
norm for all transformers. If the inductances of the two windings are not equal,
something interesting happens:
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 10000
l2 3 5 100
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 1k
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01
9.975E-05 Primary winding
freq
v(3,5) i(vi1)
6.000E+01 9.962E-01
9.962E-04 Secondary winding
Notice how the secondary voltage is approximately ten times less than the
primary voltage (0.9962 volts compared to 10 volts), while the secondary current
is approximately ten times greater (0.9962 mA compared to 0.09975 mA). What we
have here is a device that steps voltage down by a factor of ten and
current up by a factor of ten:


This is a very useful device, indeed. With it, we can easily multiply or
divide voltage and current in AC circuits. Indeed, the transformer has made
long-distance transmission of electric power a practical reality, as AC voltage
can be "stepped up" and current "stepped down" for reduced
wire resistance power losses along power lines connecting generating stations
with loads. At either end (both the generator and at the loads), voltage levels
are reduced by transformers for safer operation and less expensive equipment. A
transformer that increases voltage from primary to secondary (more secondary
winding turns than primary winding turns) is called a step-up
transformer. Conversely, a transformer designed to do just the opposite is
called a step-down transformer.
Let's re-examine a photograph shown in the previous section:

This is a step-down transformer, as evidenced by the high turn count of the
primary winding and the low turn count of the secondary. As a step-down unit,
this transformer converts high-voltage, low-current power into low-voltage,
high-current power. The larger-gauge wire used in the secondary winding is
necessary due to the increase in current. The primary winding, which doesn't
have to conduct as much current, may be made of smaller-gauge wire.
In case you were wondering, it is possible to operate either of these
transformer types backwards (powering the secondary winding with an AC source
and letting the primary winding power a load) to perform the opposite function:
a step-up can function as a step-down and visa-versa. However, as we saw in the
first section of this chapter, efficient operation of a transformer requires
that the individual winding inductances be engineered for specific operating
ranges of voltage and current, so if a transformer is to be used
"backwards" like this it must be employed within the original design
parameters of voltage and current for each winding, lest it prove to be
inefficient (or lest it be damaged by excessive voltage or current!).
Transformers are often constructed in such a way that it is not obvious
which wires lead to the primary winding and which lead to the secondary. One
convention used in the electric power industry to help alleviate confusion is
the use of "H" designations for the higher-voltage winding (the
primary winding in a step-down unit; the secondary winding in a step-up) and
"X" designations for the lower-voltage winding. Therefore, a simple
power transformer will have wires labeled "H1", "H2",
"X1", and "X2". There is usually
significance to the numbering of the wires (H1 versus H2,
etc.), which we'll explore a little later in this chapter.
The fact that voltage and current get "stepped" in opposite
directions (one up, the other down) makes perfect sense when you recall that
power is equal to voltage times current, and realize that transformers cannot produce
power, only convert it. Any device that could output more power than it took in
would violate the Law of Energy Conservation in physics, namely that
energy cannot be created or destroyed, only converted. As with the first
transformer example we looked at, power transfer efficiency is very good from
the primary to the secondary sides of the device.
The practical significance of this is made more apparent when an alternative
is considered: before the advent of efficient transformers, voltage/current
level conversion could only be achieved through the use of motor/generator sets.
A drawing of a motor/generator set reveals the basic principle involved:

In such a machine, a motor is mechanically coupled to a generator, the
generator designed to produce the desired levels of voltage and current at the
rotating speed of the motor. While both motors and generators are fairly
efficient devices, the use of both in this fashion compounds their
inefficiencies so that the overall efficiency is in the range of 90% or less.
Furthermore, because motor/generator sets obviously require moving parts,
mechanical wear and balance are factors influencing both service life and
performance. Transformers, on the other hand, are able to convert levels of AC
voltage and current at very high efficiencies with no moving parts, making
possible the widespread distribution and use of electric power we take for
granted.
In all fairness it should be noted that motor/generator sets have not
necessarily been obsoleted by transformers for all applications. While
transformers are clearly superior over motor/generator sets for AC voltage and
current level conversion, they cannot convert one frequency of AC power to
another, or (by themselves) convert DC to AC or visa-versa. Motor/generator sets
can do all these things with relative simplicity, albeit with the limitations of
efficiency and mechanical factors already described. Motor/generator sets also
have the unique property of kinetic energy storage: that is, if the motor's
power supply is momentarily interrupted for any reason, its angular momentum
(the inertia of that rotating mass) will maintain rotation of the generator for
a short duration, thus isolating any loads powered by the generator from
"glitches" in the main power system.
Looking closely at the numbers in the SPICE analysis, we should see a
correspondence between the transformer's ratio and the two inductances. Notice
how the primary inductor (l1) has 100 times more inductance than the secondary
inductor (10000 H versus 100 H), and that the measured voltage step-down ratio
was 10 to 1. The winding with more inductance will have higher voltage and less
current than the other. Since the two inductors are wound around the same core
material in the transformer (for the most efficient magnetic coupling between
the two), the parameters affecting inductance for the two coils are equal except
for the number of turns in each coil. If we take another look at our inductance
formula, we see that inductance is proportional to the square of the
number of coil turns:

So, it should be apparent that our two inductors in the last SPICE
transformer example circuit -- with inductance ratios of 100:1 -- should have
coil turn ratios of 10:1, because 10 squared equals 100. This works out to be
the same ratio we found between primary and secondary voltages and currents
(10:1), so we can say as a rule that the voltage and current transformation
ratio is equal to the ratio of winding turns between primary and secondary.

The step-up/step-down effect of coil turn ratios in a transformer is
analogous to gear tooth ratios in mechanical gear systems, transforming values
of speed and torque in much the same way:

Step-up and step-down transformers for power distribution purposes can be
gigantic in proportion to the power transformers previously shown, some units
standing as tall as a home. The following photograph shows a substation
transformer standing about twelve feet tall:

 |
REVIEW:
 |
Transformers "step up" or "step down" voltage
according to the ratios of primary to secondary wire turns.
 |

 |
A transformer designed to increase voltage from primary to secondary is
called a step-up transformer. A transformer designed to reduce
voltage from primary to secondary is called a step-down transformer.
 |
The transformation ratio of a transformer will be equal to the square
root of its primary to secondary inductance (L) ratio.
 |

|
| | | | |

Electrical isolation
Aside from the ability to easily convert between different levels of voltage
and current in AC and DC circuits, transformers also provide an extremely useful
feature called isolation, which is the ability to couple one circuit to
another without the use of direct wire connections. We can demonstrate an
application of this effect with another SPICE simulation: this time showing
"ground" connections for the two circuits, imposing a high DC voltage
between one circuit and ground through the use of an additional voltage source:

v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
v2 5 0 dc 250
l1 2 0 10000
l2 3 5 100
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 1k
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
DC voltages referenced to ground (node 0):
(1) 0.0000 (2)
0.0000 (3) 250.0000
(4) 250.0000 (5) 250.0000
AC voltages:
freq
v(2)
i(v1)
6.000E+01 1.000E+01
9.975E-05 Primary winding
freq
v(3,5) i(vi1)
6.000E+01 9.962E-01
9.962E-04 Secondary winding
SPICE shows the 250 volts DC being impressed upon the secondary circuit
elements with respect to ground, but as you can see there is no effect on the
primary circuit (zero DC voltage) at nodes 1 and 2, and the transformation of AC
power from primary to secondary circuits remains the same as before. The
impressed voltage in this example is often called a common-mode voltage
because it is seen at more than one point in the circuit with reference to the
common point of ground. The transformer isolates the common-mode voltage so that
it is not impressed upon the primary circuit at all, but rather isolated to the
secondary side. For the record, it does not matter that the common-mode voltage
is DC, either. It could be AC, even at a different frequency, and the
transformer would isolate it from the primary circuit all the same.
There are applications where electrical isolation is needed between two AC
circuit without any transformation of voltage or current levels. In these
instances, transformers called isolation transformers having 1:1
transformation ratios are used. A benchtop isolation transformer is shown in the
following photograph:

 |
REVIEW:
 |
By being able to transfer power from one circuit to another without the
use of interconnecting conductors between the two circuits, transformers
provide the useful feature of electrical isolation.
 |
Transformers designed to provide electrical isolation without stepping
voltage and current either up or down are called isolation transformers.
|
| |

Phasing
Since transformers are essentially AC devices, we need to be aware of the
phase relationships between the primary and secondary circuits. Using our SPICE
example from before, we can plot the waveshapes for the primary and secondary
circuits and see the phase relations for ourselves:
legend:
*: v(2) Primary voltage
+: v(3,5) Secondary voltage
time v(2)
(*)-----------
-10
-5
0
5 10
(+)-----------
-10
-5
0
5 10
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
0.000E+00 0.000E+00
.
.
x
. .
1.000E-03 3.675E+00
.
. . +
* . .
2.000E-03 6.803E+00
.
.
. . +
* .
3.000E-03 9.008E+00
.
.
.
. +* .
4.000E-03 9.955E+00
.
.
.
. x
5.000E-03 9.450E+00
.
.
.
. *+.
6.000E-03 7.672E+00
.
.
. . *
+ .
7.000E-03 4.804E+00
.
.
.
*.+ .
8.000E-03 1.245E+00
.
. . *
+ . .
9.000E-03 -2.474E+00 .
. * +
.
. .
1.000E-02 -5.864E+00 .
*+
.
. .
1.100E-02 -8.390E+00 . *+
.
.
. .
1.200E-02 -9.779E+00 .x
.
.
. .
1.300E-02 -9.798E+00 +*
.
.
. .
1.400E-02 -8.390E+00 . +*
.
.
. .
1.500E-02 -5.854E+00 . +
*.
.
. .
1.600E-02 -2.479E+00 .
. + *
.
. .
1.700E-02 1.246E+00
.
. .+
*
. .
1.800E-02 4.795E+00
.
.
. +
*. .
1.900E-02 7.686E+00
.
.
. . +
* .
2.000E-02 9.451E+00
.
.
.
. x .
2.100E-02 9.937E+00
.
.
.
. x
2.200E-02 9.025E+00
.
.
.
. *+ .
2.300E-02 6.802E+00
.
.
. .
*+ .
2.400E-02 3.667E+00
.
.
. * +
. .
2.500E-02 -1.487E-03 .
. *
+
. .
2.600E-02 -3.658E+00 .
. * +
.
. .
2.700E-02 -6.814E+00 . * +
.
.
. .
2.800E-02 -9.026E+00 . *+
.
.
. .
2.900E-02 -9.917E+00 *+
.
.
. .
3.000E-02 -9.511E+00 .x
.
.
. .
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
legend:
*: i(v1) Primary current
+: i(vi1) Secondary current
time i(v1)
(*)---------- -2.000E-04 -1.000E-04
0 1.000E-04 2.000E-04
(+)---------- -1.000E-03 -5.000E-04
0 5.000E-04 1.000E-03
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
0.000E+00 0.000E+00
.
.
x
. .
1.000E-03 -2.973E-05 .
. +
*.
. .
2.000E-03 -6.279E-05 . +
. *
.
. .
3.000E-03 -8.772E-05 . + .
*
.
. .
4.000E-03 -1.008E-04 +
*
.
. .
5.000E-03 -9.954E-05 .+
*
.
. .
6.000E-03 -8.522E-05 . + .
*
.
. .
7.000E-03 -5.919E-05 .
+. *
.
. .
8.000E-03 -2.500E-05 .
. +
*.
. .
9.000E-03 1.212E-05
.
. . *
+
. .
1.000E-02 4.736E-05
.
.
. *
.+ .
1.100E-02 7.521E-05
.
.
. * .
+ .
1.200E-02 9.250E-05
.
.
.
*. +.
1.300E-02 9.648E-05
.
.
.
*. +
1.400E-02 8.602E-05
.
.
. * .
+ .
1.500E-02 6.362E-05
.
.
. * .
+ .
1.600E-02 3.177E-05
.
. . *
+ . .
1.700E-02 -4.998E-06 .
.
x
. .
1.800E-02 -4.136E-05 .
. + *
.
. .
1.900E-02 -7.246E-05 . + .
*
.
. .
2.000E-02 -9.331E-05 . +
.*
.
. .
2.100E-02 -1.019E-04 +
*
.
. .
2.200E-02 -9.651E-05 . +
*
.
. .
2.300E-02 -7.749E-05 . + .
*
.
. .
2.400E-02 -4.842E-05 . .
+ *
.
. .
2.500E-02 -1.275E-05 .
.
x.
. .
2.600E-02 2.428E-05
.
. . *
+ . .
2.700E-02 5.761E-05
.
.
. *
.+ .
2.800E-02 8.261E-05
.
.
. *
. + .
2.900E-02 9.514E-05
.
.
.
*. +.
3.000E-02 9.487E-05
.
.
.
*. +.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
It would appear that both voltage and current for the two transformer
windings are in phase with each other, at least for our resistive load. This is
simple enough, but it would be nice to know which way we should connect a
transformer in order to ensure the proper phase relationships be kept. After
all, a transformer is nothing more than a set of magnetically-linked inductors,
and inductors don't usually come with polarity markings of any kind. If we were
to look at an unmarked transformer, we would have no way of knowing which way to
hook it up to a circuit to get in-phase (or 180o out-of-phase)
voltage and current:

Since this is a practical concern, transformer manufacturers have come up
with a sort of polarity marking standard to denote phase relationships. It is
called the dot convention, and is nothing more than a dot placed next to
each corresponding leg of a transformer winding:

Typically, the transformer will come with some kind of schematic diagram
labeling the wire leads for primary and secondary windings. On the diagram will
be a pair of dots similar to what is seen above. Sometimes dots will be omitted,
but when "H" and "X" labels are used to label transformer
winding wires, the subscript numbers are supposed to represent winding polarity.
The "1" wires (H1 and X1) represent where the
polarity-marking dots would normally be placed.
The similar placement of these dots next to the top ends of the primary and
secondary windings tells us that whatever instantaneous voltage polarity seen
across the primary winding will be the same as that across the secondary
winding. In other words, the phase shift from primary to secondary will be zero
degrees.
On the other hand, if the dots on each winding of the transformer do not
match up, the phase shift will be 180o between primary and secondary,
like this:

Of course, the dot convention only tells you which end of each winding is
which, relative to the other winding(s). If you want to reverse the phase
relationship yourself, all you have to do is swap the winding connections like
this:

 |
REVIEW:
 |
The phase relationships for voltage and current between primary and
secondary circuits of a transformer are direct: ideally, zero phase shift.
 |
The dot convention is a type of polarity marking for transformer
windings showing which end of the winding is which, relative to the other
windings.
|
| |

Winding configurations
Transformers are very versatile devices. The basic concept of energy
transfer between mutual inductors is useful enough between a single primary and
single secondary coil, but transformers don't have to be made with just two sets
of windings. Consider this transformer circuit:

Here, three inductor coils share a common magnetic core, magnetically
"coupling" or "linking" them together. The relationship of
winding turn ratios and voltage ratios seen with a single pair of mutual
inductors still holds true here for multiple pairs of coils. It is entirely
possible to assemble a transformer such as the one above (one primary winding,
two secondary windings) in which one secondary winding is a step-down and the
other is a step-up. In fact, this design of transformer was quite common in
vacuum tube power supply circuits, which were required to supply low voltage for
the tubes' filaments (typically 6 or 12 volts) and high voltage for the tubes'
plates (several hundred volts) from a nominal primary voltage of 110 volts AC.
Not only are voltages and currents of completely different magnitudes possible
with such a transformer, but all circuits are electrically isolated from one
another.
A photograph of a multiple-winding transformer is shown here:

This particular transformer is intended to provide both high and low
voltages necessary in an electronic system using vacuum tubes. Low voltage is
required to power the filaments of vacuum tubes, while high voltage is required
to create the potential difference between the plate and cathode elements of
each tube. One transformer with multiple windings suffices elegantly to provide
all the necessary voltage levels from a single 115 V source. The wires for this
transformer (15 of them!) are not shown in the photograph, being hidden from
view.
If electrical isolation between secondary circuits is not of great
importance, a similar effect can be obtained by "tapping" a single
secondary winding at multiple points along its length, like this:

A tap is nothing more than a wire connection made at some point on a winding
between the very ends. Not surprisingly, the winding turn/voltage magnitude
relationship of a normal transformer holds true for all tapped segments of
windings. This fact can be exploited to produce a transformer capable of
multiple ratios:

Carrying the concept of winding taps further, we end up with a
"variable transformer," where a sliding contact is moved along the
length of an exposed secondary winding, able to connect with it at any point
along its length. The effect is equivalent to having a winding tap at every turn
of the winding, and a switch with poles at every tap position:

One consumer application of the variable transformer is in speed controls
for model train sets, especially the train sets of the 1950's and 1960's. These
transformers were essentially step-down units, the highest voltage obtainable
from the secondary winding being substantially less than the primary voltage of
110 to 120 volts AC. The variable-sweep contact provided a simple means of
voltage control with little wasted power, much more efficient than control using
a variable resistor!
Moving-slide contacts are too impractical to be used in large industrial
power transformer designs, but multi-pole switches and winding taps are common
for voltage adjustment. Adjustments need to be made periodically in power
systems to accommodate changes in loads over months or years in time, and these
switching circuits provide a convenient means. Typically, such "tap
switches" are not engineered to handle full-load current, but must be
actuated only when the transformer has been de-energized (no power).
Seeing as how we can tap any transformer winding to obtain the equivalent of
several windings (albeit with loss of electrical isolation between them), it
makes sense that it should be possible to forego electrical isolation altogether
and build a transformer from a single winding. Indeed this is possible, and the
resulting device is called an autotransformer:

The autotransformer depicted above performs a voltage step-up function. A
step-down autotransformer would look something like this:

Autotransformers find popular use in applications requiring a slight boost
or reduction in voltage to a load. The alternative with a normal (isolated)
transformer would be to either have just the right primary/secondary winding
ratio made for the job or use a step-down configuration with the secondary
winding connected in series-aiding ("boosting") or series-opposing
("bucking") fashion. Primary, secondary, and load voltages are given
to illustrate how this would work.
First, the "boosting" configuration. Here, the secondary coil's
polarity is oriented so that its voltage directly adds to the primary voltage:

Next, the "bucking" configuration. Here, the secondary coil's
polarity is oriented so that its voltage directly subtracts from the primary
voltage:

The prime advantage of an autotransformer is that the same boosting or
bucking function is obtained with only a single winding, making it cheaper and
lighter to manufacture than a regular (isolating) transformer having both
primary and secondary windings.
Like regular transformers, autotransformer windings can be tapped to provide
variations in ratio. Additionally, they can be made continuously variable with a
sliding contact to tap the winding at any point along its length. The latter
configuration is popular enough to have earned itself its own name: the Variac.

Small variacs for benchtop use are popular pieces of equipment for the
electronics experimenter, being able to step household AC voltage down (or
sometimes up as well) with a wide, fine range of control by a simple twist of a
knob.
 |
REVIEW:
 |
Transformers can be equipped with more than just a single primary and
single secondary winding pair. This allows for multiple step-up and/or
step-down ratios in the same device.
 |
Transformer windings can also be "tapped:" that is,
intersected at many points to segment a single winding into sections.
 |
Variable transformers can be made by providing a movable arm that sweeps
across the length of a winding, making contact with the winding at any point
along its length. The winding, of course, has to be bare (no insulation) in
the area where the arm sweeps.
 |
An autotransformer is a single, tapped inductor coil used to step up or
step down voltage like a transformer, except without providing electrical
isolation.
 |
A Variac is a variable autotransformer.
|
| | | | |

Voltage regulation
As we saw in a few SPICE analyses earlier in this chapter, the output
voltage of a transformer varies some with varying load resistances, even with a
constant voltage input. The degree of variance is affected by the primary and
secondary winding inductances, among other factors, not the least of which
includes winding resistance and the degree of mutual inductance (magnetic
coupling) between the primary and secondary windings. For power transformer
applications, where the transformer is seen by the load (ideally) as a constant
source of voltage, it is good to have the secondary voltage vary as little as
possible for wide variances in load current.
The measure of how well a power transformer maintains constant secondary
voltage over a range of load currents is called the transformer's voltage
regulation. It can be calculated from the following formula:

"Full-load" means the point at which the transformer is operating
at maximum permissible secondary current. This operating point will be
determined primarily by the winding wire size (ampacity) and the method of
transformer cooling. Taking our first SPICE transformer simulation as an
example, let's compare the output voltage with a 1 kΩ load versus a 200
Ω load (assuming that the 200 Ω load will be our "full load"
condition). Recall if you will that our constant primary voltage was 10.00 volts
AC:
freq
v(3,5) i(vi1)
6.000E+01 9.962E+00
9.962E-03 Output with 1k ohm load
freq
v(3,5) i(vi1)
6.000E+01 9.348E+00
4.674E-02 Output with 200 ohm load
Notice how the output voltage decreases as the load gets heavier (more
current). Now let's take that same transformer circuit and place a load
resistance of extremely high magnitude across the secondary winding to simulate
a "no-load" condition:
transformer
v1 1 0 ac 10 sin
rbogus1 1 2 1e-12
rbogus2 5 0 9e12
l1 2 0 100
l2 3 5 100
k l1 l2 0.999
vi1 3 4 ac 0
rload 4 5 9e12
.ac lin 1 60 60
.print ac v(2,0) i(v1)
.print ac v(3,5) i(vi1)
.end
freq
v(2)
i(v1)
6.000E+01 1.000E+01 2.653E-04
freq
v(3,5) i(vi1)
6.000E+01 9.990E+00 1.110E-12
Output with (almost) no load
So, we see that our output (secondary) voltage spans a range of 9.990 volts
at (virtually) no load and 9.348 volts at the point we decided to call
"full load." Calculating voltage regulation with these figures, we
get:

Incidentally, this would be considered rather poor (or "loose")
regulation for a power transformer. Powering a simple resistive load like this,
a good power transformer should exhibit a regulation percentage of less than 3%.
Inductive loads tend to create a condition of worse voltage regulation, so this
analysis with purely resistive loads was a "best-case" condition.
There are some applications, however, where poor regulation is actually
desired. One such case is in discharge lighting, where a step-up transformer is
required to initially generate a high voltage (necessary to "ignite"
the lamps), then the voltage is expected to drop off once the lamp begins to
draw current. This is because discharge lamps' voltage requirements tend to be
much lower after a current has been established through the arc path. In this
case, a step-up transformer with poor voltage regulation suffices nicely for the
task of conditioning power to the lamp.
Another application is in current control for AC arc welders, which are
nothing more than step-down transformers supplying low-voltage, high-current
power for the welding process. A high voltage is desired to assist in
"striking" the arc (getting it started), but like the discharge lamp,
an arc doesn't require as much voltage to sustain itself once the air has been
heated to the point of ionization. Thus, a decrease of secondary voltage under
high load current would be a good thing. Some arc welder designs provide arc
current adjustment by means of a movable iron core in the transformer, cranked
in or out of the winding assembly by the operator. Moving the iron slug away
from the windings reduces the strength of magnetic coupling between the
windings, which diminishes no-load secondary voltage and makes for poorer
voltage regulation.
No exposition on transformer regulation could be called complete without
mention of an unusual device called a ferroresonant transformer. "Ferroresonance"
is a phenomenon associated with the behavior of iron cores while operating near
a point of magnetic saturation (where the core is so strongly magnetized that
further increases in winding current results in little or no increase in
magnetic flux).
While being somewhat difficult to describe without going deep into
electromagnetic theory, the ferroresonant transformer is a power transformer
engineered to operate in a condition of persistent core saturation. That is, its
iron core is "stuffed full" of magnetic lines of flux for a large
portion of the AC cycle so that variations in supply voltage (primary winding
current) have little effect on the core's magnetic flux density, which means the
secondary winding outputs a nearly constant voltage despite significant
variations in supply (primary winding) voltage. Normally, core saturation in a
transformer results in distortion of the sinewave shape, and the ferroresonant
transformer is no exception. To combat this side effect, ferroresonant
transformers have an auxiliary secondary winding paralleled with one or more
capacitors, forming a resonant circuit tuned to the power supply frequency. This
"tank circuit" serves as a filter to reject harmonics created by the
core saturation, and provides the added benefit of storing energy in the form of
AC oscillations, which is available for sustaining output winding voltage for
brief periods of input voltage loss (milliseconds' worth of time, but certainly
better than nothing).

In addition to blocking harmonics created by the saturated core, this
resonant circuit also "filters out" harmonic frequencies generated by
nonlinear (switching) loads in the secondary winding circuit and any harmonics
present in the source voltage, providing "clean" power to the load.
Ferroresonant transformers offer several features useful in AC power
conditioning: constant output voltage given substantial variations in input
voltage, harmonic filtering between the power source and the load, and the
ability to "ride through" brief losses in power by keeping a reserve
of energy in its resonant tank circuit. These transformers are also highly
tolerant of excessive loading and transient (momentary) voltage surges. They are
so tolerant, in fact, that some may be briefly paralleled with unsynchronized AC
power sources, allowing a load to be switched from one source of power to
another in a "make-before-break" fashion with no interruption of power
on the secondary side!
Unfortunately, these devices have equally noteworthy disadvantages: they
waste a lot of energy (due to hysteresis losses in the saturated core),
generating significant heat in the process, and are intolerant of
frequency variations, which means they don't work very well when powered by
small engine-driven generators having poor speed regulation. Voltages produced
in the resonant winding/capacitor circuit tend to be very high, necessitating
expensive capacitors and presenting the service technician with very dangerous
working voltages. Some applications, though, may prioritize the ferroresonant
transformer's advantages over its disadvantages. Semiconductor circuits exist to
"condition" AC power as an alternative to ferroresonant devices, but
none can compete with this transformer in terms of sheer simplicity.
 |
REVIEW:
 |
Voltage regulation is the measure of how well a power transformer
can maintain constant secondary voltage given a constant primary voltage and
wide variance in load current. The lower the percentage (closer to zero),
the more stable the secondary voltage and the better the regulation it will
provide.
 |
A ferroresonant transformer is a special transformer designed to
regulate voltage at a stable level despite wide variation in input voltage.
|
| |

Special transformers and applications
Because transformers can step voltage and current to different levels, and
because power is transferred equivalently between primary and secondary
windings, they can be used to "convert" the impedance of a load to a
different level. That last phrase deserves some explanation, so let's
investigate what it means.
The purpose of a load (usually) is to do something productive with the power
it dissipates. In the case of a resistive heating element, the practical purpose
for the power dissipated is to heat something up. Loads are engineered to safely
dissipate a certain maximum amount of power, but two loads of equal power rating
are not necessarily identical. Consider these two 1000 watt resistive heating
elements:

Both heaters dissipate exactly 1000 watts of power, but they do so at
different voltage and current levels (either 250 volts and 4 amps, or 125 volts
and 8 amps). Using Ohm's Law to determine the necessary resistance of these
heating elements (R=E/I), we arrive at figures of 62.5 Ω and 15.625 Ω,
respectively. If these are AC loads, we might refer to their opposition to
current in terms of impedance rather than plain resistance, although in this
case that's all they're composed of (no reactance). The 250 volt heater would be
said to be a higher impedance load than the 125 volt heater.
If we desired to operate the 250 volt heater element directly on a 125 volt
power system, we would end up being disappointed. With 62.5 Ω of impedance
(resistance), the current would only be 2 amps (I=E/R; 125/62.5), and the power
dissipation would only be 250 watts (P=IE; 125 x 2), or one-quarter of its rated
power. The impedance of the heater and the voltage of our source would be
mismatched, and we couldn't obtain the full rated power dissipation from the
heater.
All hope is not lost, though. With a step-up transformer, we could operate
the 250 volt heater element on the 125 volt power system like this:

The ratio of the transformer's windings provides the voltage step-up and
current step-down we need for the otherwise mismatched load to operate properly
on this system. Take a close look at the primary circuit figures: 125 volts at 8
amps. As far as the power supply "knows," it's powering a 15.625
Ω (R=E/I) load at 125 volts, not a 62.5 Ω load! The voltage and
current figures for the primary winding are indicative of 15.625 Ω load
impedance, not the actual 62.5 Ω of the load itself. In other words, not
only has our step-up transformer transformed voltage and current, but it has
transformed impedance as well.
The transformation ratio of impedance is the square of the voltage/current
transformation ratio, the same as the winding inductance ratio:

This concurs with our example of the 2:1 step-up transformer and the
impedance ratio of 62.5 Ω to 15.625 Ω (a 4:1 ratio, which is 2:1
squared). Impedance transformation is a highly useful ability of transformers,
for it allows a load to dissipate its full rated power even if the power system
is not at the proper voltage to directly do so.
Recall from our study of network analysis the Maximum Power Transfer
Theorem, which states that the maximum amount of power will be dissipated by
a load resistance when that load resistance is equal to the Thevenin/Norton
resistance of the network supplying the power. Substitute the word
"impedance" for "resistance" in that definition and you have
the AC version of that Theorem. If we're trying to obtain theoretical maximum
power dissipation from a load, we must be able to properly match the load
impedance and source (Thevenin/Norton) impedance together. This is generally
more of a concern in specialized electric circuits such as radio
transmitter/antenna and audio amplifier/speaker systems. Let's take an audio
amplifier system and see how it works:

With an internal impedance of 500 Ω, the amplifier can only deliver
full power to a load (speaker) also having 500 Ω of impedance. Such a load
would drop higher voltage and draw less current than an 8 Ω speaker
dissipating the same amount of power. If an 8 Ω speaker were connected
directly to the 500 Ω amplifier as shown, the impedance mismatch
would result in very poor (low peak power) performance. Additionally, the
amplifier would tend to dissipate more than its fair share of power in the form
of heat trying to drive the low impedance speaker.
To make this system work better, we can use a transformer to match these
mismatched impedances. Since we're going from a high impedance (high voltage,
low current) supply to a low impedance (low voltage, high current) load, we'll
need to use a step-down transformer:

To obtain an impedance transformation ratio of 500:8, we would need a
winding ratio equal to the square root of 500:8 (the square root of 62.5:1, or
7.906:1). With such a transformer in place, the speaker will load the amplifier
to just the right degree, drawing power at the correct voltage and current
levels to satisfy the Maximum Power Transfer Theorem and make for the most
efficient power delivery to the load. The use of a transformer in this capacity
is called impedance matching.
Anyone who has ridden a multi-speed bicycle can intuitively understand the
principle of impedance matching. A human's legs will produce maximum power when
spinning the bicycle crank at a particular speed (about 60 to 90 revolution per
minute). Above or below that rotational speed, human leg muscles are less
efficient at generating power. The purpose of the bicycle's "gears" is
to impedance-match the rider's legs to the riding conditions so that they always
spin the crank at the optimum speed.
If the rider attempts to start moving while the bicycle is shifted into its
"top" gear, he or she will find it very difficult to get moving. Is it
because the rider is weak? No, it's because the high step-up ratio of the
bicycle's chain and sprockets in that top gear presents a mismatch between the
conditions (lots of inertia to overcome) and their legs (needing to spin at
60-90 RPM for maximum power output). On the other hand, selecting a gear that is
too low will enable the rider to get moving immediately, but limit the top speed
they will be able to attain. Again, is the lack of speed an indication of
weakness in the bicyclist's legs? No, it's because the lower speed ratio of the
selected gear creates another type of mismatch between the conditions (low load)
and the rider's legs (losing power if spinning faster than 90 RPM). It is much
the same with electric power sources and loads: there must be an impedance match
for maximum system efficiency. In AC circuits, transformers perform the same
matching function as the sprockets and chain ("gears") on a bicycle to
match otherwise mismatched sources and loads.
Impedance matching transformers are not fundamentally different from any
other type of transformer in construction or appearance. A small
impedance-matching transformer (about two centimeters in width) for
audio-frequency applications is shown in the following photograph:

Another impedance-matching transformer can be seen on this printed circuit
board, in the upper right corner, to the immediate left of resistors R2
and R1. It is labeled "T1":

Transformers can also be used in electrical instrumentation systems. Due to
transformers' ability to step up or step down voltage and current, and the
electrical isolation they provide, they can serve as a way of connecting
electrical instrumentation to high-voltage, high current power systems. Suppose
we wanted to accurately measure the voltage of a 13.8 kV power system (a very
common power distribution voltage in American industry):

Designing, installing, and maintaining a voltmeter capable of directly
measuring 13,800 volts AC would be no easy task. The safety hazard alone of
bringing 13.8 kV conductors into an instrument panel would be severe, not to
mention the design of the voltmeter itself. However, by using a precision
step-down transformer, we can reduce the 13.8 kV down to a safe level of voltage
at a constant ratio, and isolate it from the instrument connections, adding an
additional level of safety to the metering system:

Now the voltmeter reads a precise fraction, or ratio, of the actual system
voltage, its scale set to read as though it were measuring the voltage directly.
The transformer keeps the instrument voltage at a safe level and electrically
isolates it from the power system, so there is no direct connection between the
power lines and the instrument or instrument wiring. When used in this capacity,
the transformer is called a Potential Transformer, or simply PT.
Potential transformers are designed to provide as accurate a voltage
step-down ratio as possible. To aid in precise voltage regulation, loading is
kept to a minimum: the voltmeter is made to have high input impedance so as to
draw as little current from the PT as possible. As you can see, a fuse has been
connected in series with the PTs primary winding, for safety and ease of
disconnecting the PT from the circuit.
A standard secondary voltage for a PT is 120 volts AC, for full-rated power
line voltage. The standard voltmeter range to accompany a PT is 150 volts,
full-scale. PTs with custom winding ratios can be manufactured to suit any
application. This lends itself well to industry standardization of the actual
voltmeter instruments themselves, since the PT will be sized to step the system
voltage down to this standard instrument level.
Following the same line of thinking, we can use a transformer to step down
current through a power line so that we are able to safely and easily measure
high system currents with inexpensive ammeters. Of course, such a transformer
would be connected in series with the power line, like this:

Note that while the PT is a step-down device, the Current Transformer
(or CT) is a step-up device (with respect to voltage), which is what is
needed to step down the power line current. Quite often, CTs are built as
donut-shaped devices through which the power line conductor is run, the power
line itself acting as a single-turn primary winding:

Some CTs are made to hinge open, allowing insertion around a power conductor
without disturbing the conductor at all. The industry standard secondary current
for a CT is a range of 0 to 5 amps AC. Like PTs, CTs can be made with custom
winding ratios to fit almost any application. Because their "full
load" secondary current is 5 amps, CT ratios are usually described in terms
of full-load primary amps to 5 amps, like this:

The "donut" CT shown in the photograph has a ratio of 50:5. That
is, when the conductor through the center of the torus is carrying 50 amps of
current (AC), there will be 5 amps of current induced in the CT's winding.
Because CTs are designed to be powering ammeters, which are low-impedance
loads, and they are wound as voltage step-up transformers, they should never, ever
be operated with an open-circuited secondary winding. Failure to heed this
warning will result in the CT producing extremely high secondary voltages,
dangerous to equipment and personnel alike. To facilitate maintenance of ammeter
instrumentation, short-circuiting switches are often installed in parallel with
the CT's secondary winding, to be closed whenever the ammeter is removed for
service:

Though it may seem strange to intentionally short-circuit a power
system component, it is perfectly proper and quite necessary when working with
current transformers.
Another kind of special transformer, seen often in radio-frequency circuits,
is the air core transformer. True to its name, an air core transformer
has its windings wrapped around a nonmagnetic form, usually a hollow tube of
some material. The degree of coupling (mutual inductance) between windings in
such a transformer is many times less than that of an equivalent iron-core
transformer, but the undesirable characteristics of a ferromagnetic core (eddy
current losses, hysteresis, saturation, etc.) are completely eliminated. It is
in high-frequency applications that these effects of iron cores are most
problematic.
One notable example of air-core transformer is the Tesla Coil, named
after the Serbian electrical genius Nikola Tesla, who was also the inventor of
the rotating magnetic field AC motor, polyphase AC power systems, and many
elements of radio technology. The Tesla Coil is a resonant, high-frequency
step-up transformer used to produce extremely high voltages. One of Tesla's
dreams was to employ his coil technology to distribute electric power without
the need for wires, simply broadcasting it in the form of radio waves which
could be received and conducted to loads by means of antennas. The basic
schematic for a Tesla Coil looks like this:

The capacitor, in conjunction with the transformer's primary winding, forms
a tank circuit. The secondary winding is wound in close proximity to the
primary, usually around the same nonmagnetic form. Several options exist for
"exciting" the primary circuit, the simplest being a high-voltage,
low-frequency AC source and spark gap:

The purpose of the high-voltage, low-frequency AC power source is to
"charge" the primary tank circuit. When the spark gap fires, its low
impedance acts to complete the capacitor/primary coil tank circuit, allowing it
to oscillate at its resonant frequency. The "RFC" inductors are
"Radio Frequency Chokes," which act as high impedances to prevent the
AC source from interfering with the oscillating tank circuit.
The secondary side of the Tesla coil transformer is also a tank circuit,
relying on the parasitic (stray) capacitance existing between the discharge
terminal and earth ground to complement the secondary winding's inductance. For
optimum operation, this secondary tank circuit is tuned to the same resonant
frequency as the primary circuit, with energy exchanged not only between
capacitors and inductors during resonant oscillation, but also back-and-forth
between primary and secondary windings. The visual results are spectacular:

Tesla Coils find application primarily as novelty devices, showing up in
high school science fairs, basement workshops, and the occasional low budget
science-fiction movie.
It should be noted that Tesla coils can be extremely dangerous devices.
Burns caused by radio-frequency ("RF") current, like all electrical
burns, can be very deep, unlike skin burns caused by contact with hot objects or
flames. Although the high-frequency discharge of a Tesla coil has the curious
property of being beyond the "shock perception" frequency of the human
nervous system, this does not mean Tesla coils cannot hurt or even kill you! I
strongly advise seeking the assistance of an experienced Tesla coil experimenter
if you would embark on building one yourself.
So far, we've explored the transformer as a device for converting different
levels of voltage, current, and even impedance from one circuit to another. Now
we'll take a look at it as a completely different kind of device: one that
allows a small electrical signal to exert control over a much larger
quantity of electrical power. In this mode, a transformer acts as an amplifier.
The device I'm referring to is called a saturable-core reactor, or
simply saturable reactor. Actually, it is not really a transformer at
all, but rather a special kind of inductor whose inductance can be varied by the
application of a DC current through a second winding wound around the same iron
core. Like the ferroresonant transformer, the saturable reactor relies on the
principle of magnetic saturation. When a material such as iron is completely
saturated (that is, all its magnetic domains are lined up with the applied
magnetizing force), additional increases in current through the magnetizing
winding will not result in further increases of magnetic flux.
Now, inductance is the measure of how well an inductor opposes changes in
current by developing a voltage in an opposing direction. The ability of an
inductor to generate this opposing voltage is directly connected with the change
in magnetic flux inside the inductor resulting from the change in current, and
the number of winding turns in the inductor. If an inductor has a saturated
core, no further magnetic flux will result from further increases in current,
and so there will be no voltage induced in opposition to the change in current.
In other words, an inductor loses its inductance (ability to oppose changes in
current) when its core becomes magnetically saturated.
If an inductor's inductance changes, then its reactance (and impedance) to
AC current changes as well. In a circuit with a constant voltage source, this
will result in a change in current:

A saturable reactor capitalizes on this effect by forcing the core into a
state of saturation with a strong magnetic field generated by current through
another winding. The reactor's "power" winding is the one carrying the
AC load current, and the "control" winding is one carrying a DC
current strong enough to drive the core into saturation:

The strange-looking transformer symbol shown in the above schematic
represents a saturable-core r |